![ComAp ID-Lite Скачать руководство пользователя страница 148](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907148.webp)
ID-FLX Lite & Telecom Global Guide
148
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
10
-
Step
1
Comm object
13358
Related applications
Description
High level protection delay for Wrn and Sd of AIN5.
Note:
Analog input 5 is fully configurable and it is voltage type of input with range 0-40 V.
AIN5 HighDel
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U12]
Default value
20
-
Step
1
Comm object
9259
Related applications
Description
Warning limit level for AIN6.
AIN6 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [-]
Default value
10
-
Step
1
Comm object
9260
Related applications
Description
Shutdown limit level for AIN6.
AIN6 Level 2
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
10
-
Step
1
Comm object
9261
Related applications
Description
Delay for Wrn/Sd AIN6 alarm.
AIN6 Del
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...