ID-FLX Lite & Telecom Global Guide
60
Engine RPM two/three levels switching
Continuing example above …. closed
,
,
ramps the Engine RPM to the selected setpoint level. … i.e. switched/ramped to another three levels.
Note:
If there is more than one Speed Sel Setpoint activated,
has higher priority, then
and after
Note:
Necessary condition:
= OFF and controller MAN mode.
Engine RPM by Up/Down buttons settings
RPM adjusted in examples above can be changed by
/
when
the
= DISABLED.
Note:
Necessary condition:
= OFF and controller MAN mode.
Engine RPM continuous change (using potentiometer)
Adjust
= AI1-9 … to corresponding controller or extension module analog input.
Configure this Analog input - sensor characteristic in RPM or Percentage (expected potentiometer resistance
2.5 kΩ in example below).
is active.