#2 Phillips screwdriver
Tools/Equipment
•
NTP-G252 Install the ONS 15454 M6 Shelf , on page 24
.
•
NTP-G259 Open and Remove the Standard Door of the ONS 15454 M6
Shelf , on page 57
• Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, see the
Electrostatic Discharge and Grounding Guide
for Cisco CPT and Cisco ONS Platforms
Prerequisite Procedures
Required
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
The node can temporarily work with both 15454-M6-AC and 15454-M6-AC2 power module units installed
on the ONS 15454 M6 shelf. However, during regular operation, the shelf must have either the 15454-M6-AC
or 15454-M6-AC2 power module, but not both.
Caution
Insert the AC power module in Slot A or Slot B, or both (see the following figure).
Tip
While inserting the AC power module, apply insertion force only above the hook and not on the air filter (see
the following figure).
Note
Installing the ONS 15454 M6 Shelf
86
Installing the ONS 15454 M6 Shelf
DLP-G569 Install the AC Power Module in the ONS 15454 M6 Shelf