Figure 19: Pre-assembled air plenum for ANSI 23-inch configuration
Step 10
Install the pre-assembled air plenums in the ANSI 23-inch rack or cabinet.
Step 11
Check the length between the top and bottom horizontal air plenums where the chassis will be installed. The
length must be not less than 10.5 inches (267 mm). If the length is less, adjust the position of the top horizontal
plenum.
Step 12
Install the empty ONS 15454 M6 chassis between the horizontal plenums.
Step 13
Return to your originating procedure (NTP).