Use only the fastening hardware provided with the ONS 15454 M6 to prevent loosening, deterioration, and
electromechanical corrosion of the hardware and joined material.
Caution
When mounting the ONS 15454 M6 in a frame with a nonconductive coating (such as paint, lacquer, or
enamel) either use the thread-forming screws provided with the ONS 15454 M6 ship kit, or remove the coating
from the threads to ensure electrical continuity.
Caution
Procedure
Step 1
Place the mounting bracket flush against the shelf as shown in the following figure.
Step 2
Align the mounting bracket screw holes against the shelf screw holes.
Step 3
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 4
Repeat steps 1 through 3 for the mounting bracket on the opposite side.
Figure 33: Mounting the Brackets on the ONS 15454 M6 Shelf for ETSI Rack Configuration
Step 5
Return to your originating procedure (NTP).
Installing the ONS 15454 M6 Shelf
35
Installing the ONS 15454 M6 Shelf
DLP-G562 Mounting the Brackets on the ONS 15454 M6 Shelf for ETSI Rack Configuration