53
Instruction Manual
AFQm
6.13.- ALARMS
Note:
This screen is not visible on the
“slave”
devices.
In this screen,
Figure 53
, the alarms that have occurred are shown.
Figure 53: Alarms�
A brief description of the alarm is displayed on the screen, as well as the date and time at which
it occurred.
Press the
key to delete the alarm log.
Table 20
shows the messages that could appear on the device.
If the cause of the alarm disappears, the device will be reconnected automatically.
If the same alarm is triggered 5 times during a 1-hour period, the automatic device reconnection
function will be disabled.
The
key rearms the device if the cause of the alarm has disappeared or has been
resolved.
Use the
and
keys to navigate through the different display screens.
Table 20:Alarm messages�
Alarm messages
Overcurrent L1/L2/L3
Description
The
AFQm
current is too high.
Corrective
action
This alarm may be associated with transients and noise in the power supply voltage. Check
the quality of the power supply voltage. If it continues, contact the
TAS
.
Mains overvoltage L1/L2/L3
Description
The mains voltage is too high.
Corrective
action
This alarm may be associated with transients and noise in the power supply voltage, or with
incorrect mains voltage values. Check the configuration. Check the quality of the power supply
voltage. If it continues, contact the
TAS�
High temp IGBT
Description
The temperature of the power module is very high.
Corrective
action
Check that the fans are working. Clean or replace them if necessary. If it continues, contact
the
TAS�
Содержание AFQm Series
Страница 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 19B...
Страница 2: ...2 AFQm Instruction Manual...
Страница 103: ...103 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 98 Dimensions Cabinet type AFQm...
Страница 105: ...105 Instruction Manual AFQm 14 CE CERTIFICATE...
Страница 106: ...106 AFQm Instruction Manual...
Страница 107: ...107 Instruction Manual AFQm...