68
AFQm
Instruction Manual
7.8.- ALARMS
Note:
This screen is not visible on the
“slave”
devices.
In this screen,
Figure 71
, the enabling or disabling of the resonance alarm is selected.
Figure 71:
Configuration screen: Alarms.
If the control algorithm was selected in the
Frequency mode
and this alarm is
enabled
, when
the device detects a potential resonance on an harmonic, it disables said harmonic and gener-
ates an alarm, but it continues filtering the rest of the harmonics.
If the alarm is
disabled
, the device may interpret a resonance as an overload and continue
filtering the harmonic.
This option is
enabled
by default and it is recommended not to disable it.
Before
disabling
the resonance alarm, it is essential to make sure there is no
resonating current between the active filter and the load. Resonating currents can
damage the active filter and other devices connected to the installation.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration
values.