10-3
10.2 Jog operation
Group
Display
Parameter Name
Setting
Range
Default Unit
Function
group 1
F20
[Jog frequency]
-
0 ~ 400
10.00
Hz
I/O
group
I21
[Multi-function input
terminal P5 define]
4
0 ~ 24
4
Set the desired jog frequency in F20.
Select a terminal from P1 - P8 to use for this setting.
If P5 is set for Jog operation, set I21 to 4 {Jog}.
Jog frequency can be set within the range of F21 - [Max frequency] and F
23
– [Start
frequency].
Jog operation overrides all other operations except Dwell operation. Therefore, if
Jog frequency command is entered in the middle of Multi-Step, Up-Down or 3-wire
operation, operation is executed at Jog frequency.
The above diagram is an example when Multi-function input is set to NPN mode.
wX
w\
jt
GmGaGpX^GdGW
qvnGaGpYXd[
P5 (JOG)
Run
command(FX)
Frequency
F20