![Cerus Industrial Titan CI-001-GS2 Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/cerus-industrial/titan-ci-001-gs2/titan-ci-001-gs2_installation-operation-and-maintenance-manual_2583981049.webp)
7-4
z
Function group 1
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
Page
This parameter sets the highest
frequency the inverter can output.
It is frequency reference for
Accel/Decel (See H70)
F21
1)
[Max
frequency]
40 ~ 400
[Hz]
Caution: Any frequency cannot be
set above Max frequency except
Base frequency.
60.00
X
9-21
F22
[Base
frequency]
30 ~ 400
[Hz]
The inverter outputs its rated
voltage to the motor at this
frequency (see motor nameplate).
60.00
X
9-17
F23
[Start
frequency]
0 ~ 10
[Hz]
The inverter starts to output its
voltage at this frequency.
It is the frequency low limit.
0.50
X
9-21
F24
[Frequency
high/low limit
select]
0 ~ 1
This parameter sets high and low
limit of run frequency.
0
X
F25
2)
[Frequency
high limit]
0 ~ 400
[Hz]
This parameter sets high limit of
the run frequency.
It cannot be set above F21 –
[Max frequency].
60.00
X
9-21
F26
[Frequency
low limit]
0.1 ~ 400
[Hz]
This parameter sets low limit of
the run frequency.
It cannot be set above F25 -
[Frequency high limit] and below
F23 – [Start frequency].
0.50
X
0
Manual torque boost
F27
[Torque
Boost select]
0 ~ 1
1
Auto torque boost
0
X
9-19
F28
[Torque boost
in forward
direction]
This parameter sets the amount
of torque boost applied to a motor
during forward run.
It is set in percent of Max output
voltage.
2
X
9-19
F29
[Torque boost
in reverse
direction]
0 ~ 15
[%]
This parameter sets the amount
of torque boost applied to a motor
during reverse run.
It is set as a percent of Max
output voltage
2
X
9-19
1)
: If H40 is set to 3 (Sensorless vector), Max. frequency is settable up to 300Hz.
2)
: Only displayed when F24 (Frequency high/low limit select) is set to 1.
Содержание Titan CI-001-GS2
Страница 1: ...D GS S Compact Space Ve VFD Frequency and 5 5 5 5 8...
Страница 13: ...1 4 Notes...
Страница 16: ...2 3 2 2 Dimensions CI 002 GS2 4 CI 001 GS2 4...
Страница 17: ...2 4 CI 003 GS2 4 CI 005 GS2 4 CI 007 GS2 4 CI 010 GS2 4 H W D W1 A A H1 W1 B B...
Страница 19: ......
Страница 25: ...3 6 5 5 7 5 kW 5 5 mm2 M4 3 5 mm2 M4...
Страница 45: ...6 4 Notes...
Страница 68: ...CHAPTER 8 CONTROL BLOCK DIAGRAM m G k G h Vk Vm w t t...
Страница 71: ...8 4 Notes...
Страница 119: ...10 26 Notes...
Страница 141: ...12 10 Ex 2 100 2 _ _ 1 _ _ _ 76 u steady T acc T steady T dec T dec T H m U X Y...
Страница 159: ...13 18 Notes...
Страница 169: ...15 4...
Страница 170: ...15 5 Notes...
Страница 171: ......