9-10
z
Rotating direction select via –10 ~ +10[V] input of V1 terminal
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive group
frq
[Frequency setting]
2
0 ~ 7
0
drv
[Drive mode]
-
0 ~ 3
1
Set
frq
to 2.
Inverter is operating as the table below regardless of Drive mode setting.
FWD RUN Command
REV RUN Command
0 ~ +10 [V]
FWD RUN
REV RUN
-10 ~ 0 [V]
REV RUN
FWD RUN
Motor runs in Forward direction when input voltage to V1-CM is 0~10[V] and FWD
RUN command is active. When input voltage polarity is reversed to –10~0[V] during
FWD RUN, motor decelerates to stop and runs in reverse direction.
When input voltage to V1-CM is 0~10[V] and REV RUN command is active, motor
runs in Reverse direction and if -10~0[V] is input, motor rotating direction is reverse.
z
FX/RX Run Disable
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive group
drC
[Direction of motor
rotation select]
-
F, r
F
Function group 1
F 1
[Forward/Reverse run
disable]
-
0 ~ 2
0
Select the direction of motor rotation.
0: Forward and Reverse run enable
1: Forward run disable
2: Reverse run disable
Содержание Titan CI-001-GS2
Страница 1: ...D GS S Compact Space Ve VFD Frequency and 5 5 5 5 8...
Страница 13: ...1 4 Notes...
Страница 16: ...2 3 2 2 Dimensions CI 002 GS2 4 CI 001 GS2 4...
Страница 17: ...2 4 CI 003 GS2 4 CI 005 GS2 4 CI 007 GS2 4 CI 010 GS2 4 H W D W1 A A H1 W1 B B...
Страница 19: ......
Страница 25: ...3 6 5 5 7 5 kW 5 5 mm2 M4 3 5 mm2 M4...
Страница 45: ...6 4 Notes...
Страница 68: ...CHAPTER 8 CONTROL BLOCK DIAGRAM m G k G h Vk Vm w t t...
Страница 71: ...8 4 Notes...
Страница 119: ...10 26 Notes...
Страница 141: ...12 10 Ex 2 100 2 _ _ 1 _ _ _ 76 u steady T acc T steady T dec T dec T H m U X Y...
Страница 159: ...13 18 Notes...
Страница 169: ...15 4...
Страница 170: ...15 5 Notes...
Страница 171: ......