9-4
z
Frequency setting via 0 ~ 10 [V] input or Terminal Potentiometer
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive group
0.00
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
3
0 ~ 7
0
I 6
[Filter time constant for V1
input]
10
0 ~ 9999
10
I 7
[V1 input Min voltage]
-
0 ~ 10
0
V
I 8
[Frequency corresponding
to I 7]
-
0 ~ 400
0.00
Hz
I 9
[V1 input max voltage]
-
0 ~ 10
10
V
I/O group
I10
[Frequency corresponding
to I 9]
-
0 ~ 400
60.00
Hz
Select 3 in Frq code of Drive group.
0-10V can be directly applied from an external controller or a potentiometer connected on
terminals VR, V1 and CM.
Wire the terminals as shown below and refer to page 9-3 for I 6 ~ I 10.
z
Frequency setting via 0 ~ 20 [mA] input
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive
group
0.00
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
4
0 ~ 7
0
I/O
group
I11
[Filter time constant for I input]
10
0 ~ 9999
10
I12
[I input minimum current]
-
0 ~ 20
4
mA
I13
[Frequency corresponding to I12] -
0 ~ 400
0.00
Hz
I14
[I input max current]
-
0 ~ 20
20
mA
I15
[Frequency corresponding to I14] -
0 ~ 400
60.00
Hz
Select 4 in Frq code of Drive group.
Frequency is set via 0~20mA input between I and CM terminal.
}y
}X
jt
~GG
}X
jt
WG¥GXW}GGGG
Содержание Titan CI-001-GS2
Страница 1: ...D GS S Compact Space Ve VFD Frequency and 5 5 5 5 8...
Страница 13: ...1 4 Notes...
Страница 16: ...2 3 2 2 Dimensions CI 002 GS2 4 CI 001 GS2 4...
Страница 17: ...2 4 CI 003 GS2 4 CI 005 GS2 4 CI 007 GS2 4 CI 010 GS2 4 H W D W1 A A H1 W1 B B...
Страница 19: ......
Страница 25: ...3 6 5 5 7 5 kW 5 5 mm2 M4 3 5 mm2 M4...
Страница 45: ...6 4 Notes...
Страница 68: ...CHAPTER 8 CONTROL BLOCK DIAGRAM m G k G h Vk Vm w t t...
Страница 71: ...8 4 Notes...
Страница 119: ...10 26 Notes...
Страница 141: ...12 10 Ex 2 100 2 _ _ 1 _ _ _ 76 u steady T acc T steady T dec T dec T H m U X Y...
Страница 159: ...13 18 Notes...
Страница 169: ...15 4...
Страница 170: ...15 5 Notes...
Страница 171: ......