Table 6 — Protective Safety Limits and Control Settings (cont)
MONITORED PARAMETER
STATE
LIMIT
COMMENTS
LOW PRESSURE
142
OIL PRESSURE DELTA P < 18 PSID and startup
complete
Preset Alert
OIL - PRESSURE SENSOR
FAULT
227
OIL PRESSURE DELTA P > 4 PSI immediately
before oil pump turned on
Preset Alarm
OIL - LOW TEMPERATURE
105
OIL SUMP TEMP < 150 deg F and [OIL SUMP
TEMP < CALC EVAP SAT TEMP + 50 deg F(27.8
deg C)]
Prestart Alert
LINE VOLTAGE - HIGH
211/145
Line voltage > 150 % MOTOR RATED LINE VOLT-
AGE for 1 second
Preset Alarm / Alert if Autorestart is
enabled
211/145
Line voltage > 115 % MOTOR RATED LINE VOLT-
AGE for 10 seconds
211/145
Line voltage > OVERVOLTAGE THRESHOLD for
OVER/UNDER VOLTAGE TIME
Configure OVERVOLTAGE THRESHOLD
and OVER/UNDER VOLT TIME in ISM_-
CONF screen
108
AVERAGE LINE VOLTAGE > OVERVOLTAGE
THRESHOLD
Configure OVERVOLTAGE THRESHOLD
in ISM_CONF screen
LINE VOLTAGE - LOW
212/146
AVERAGE LINE VOLTAGE < 75% MOTOR RATED
LINE VOLTAGE for 1 second OR AVERAGE LINE
VOLTAGE < 80% MOTOR RATED LINE VOLTAGE
for 5 seconds OR AVERAGE LINE VOLTAGE <
85% MOTOR RATED LINE VOLTAGE for 10 sec-
onds OR AVERAGE LINE VOLTAGE < UNDER-
VOLTAGE THRESHOLD for > OVER/UNDER
VOLTAGE TIME
Preset Alarm/Alert Configure UNDER-
VOLTAGE THRESHOLD and OVER/
UNDER VOLT TIME in ISM_CONF screen
107
PERCENT LINE VOLTAGE < UNDERVOLTAGE
THRESHOLD
Prestart Alert, Configure UNDERVOLTAGE
THRESHOLD in ISM_CONF screen
LINE VOLTAGE - IMBALANCE
216
Line Voltage Imbalance > VOLTAGE % IMBAL-
ANCE for > VOLTAGE IMBALANCE TIME
Configure VOLTAGE % IMBALANCE and
VOLTAGE IMBALANCE TIME in ISM_-
CONF screen
LINE CURRENT -SINGLE CYCLE
DROPOUT
210/144
Line Voltage on 2 Phases < 50% for 1 Cycle
Preset Alarm/Prestart Alert, Configure
SINGLE CYCLE DROPOUT in ISM_CONF
screen
CURRENT IMBALANCE
215
Line Current Imbalance > CURRENT % IMBAL-
ANCE for > CURRENT IMBALANCE TIME
Configure CURRENT % IMBALANCE and
CURRENT IMBALANCE TIME in ISM_-
CONF screen
POWER - LINE FREQUENCY OUT
OF RANGE
222
LINE FREQUENCY [<56 Hz or > 64 Hz] (60 Hz),
LINE FREQUENCY [<46 Hz or > 54 Hz] (50 HZ)
Preset Alarm
PHASE LOSS
209/143
Any LINE VOLTAGE PHASE < 50% MOTOR
RATED LINE VOLTAGE
Condition must persist for 2 seconds
209/143
Minimum LINE CURRENT PHASE < 1/16 Maxi-
mum LINE CURRENT PHASE and Maximum LINE
CURRENT PHASE > 5% MOTOR RATED LOAD
AMPS
Condition must persist for 1 seconds
ISM POWER ON RESET
213/147
Loss of control power (brownout < 97 volts) to ISM
for excessive time period
Preset Alarm
ICVC POWER ON RESET
214/148
Loss of control power (<18 volts) to ICVC for exces-
sive time period
Preset Alarm
COMMUNICATION - LOSS OF
COMMUNICATION
242
SIO Communication between ICVC and CCM lost
for more than 5 seconds
Preset Alarm
LOSS OF COMMUNICATION
WITH STARTER
241
SIO Communication between ICVC and ISM lost
for more than 5 seconds
Preset Alarm
1M AUX. CONTACT FAULT
200
Aux. contacts open with 1CR = ON + 3 sec.
Preset Alarm
2M AUX. CONTACT FAULT
201
Aux. contacts open with 1CR/Transition = ON + 3
Sec
Preset Alarm
STARTER FAULT
206
Starter Fault = Open w/1CR = ON
Preset Alarm, Check starter safety circuit
COMPRESSOR SURGE
238
> 4 surge protection counts within SURGE TIME
PERIOD and VFD SPEED > 90%
Preset Alarm, Configure SURGE DELTA%
AMPS and SURGE TIME PERIOD in
OPTIONS screen
SURGE
236
> 4 surge protection counts within SURGE TIME
PERIOD and VFD SPEED < 90%
Preset Alarm, Configure SURGE DELTA%
AMPS and SURGE TIME PERIOD in
OPTIONS screen
Содержание AquaEdge 19XR series
Страница 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Страница 150: ...150 Fig 62 PIC II Control Panel Wiring Schematic Frame 2 3 4 and E Compressors without Split Ring Diffuser a19 1870 ...
Страница 152: ...152 a19 1871 Fig 63 PIC II Control Panel Wiring Schematic Frame 4 and 5 Compressors with Split Ring Diffuser ...
Страница 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Страница 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Страница 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Страница 163: ...163 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont a19 1880 ...
Страница 176: ...176 CONTINUED ON NEXT PAGE Fig 71 Typical Medium Voltage Variable Frequency Drive VFD Wiring Schematic cont a19 2064 ...
Страница 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Страница 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...