38
Table 3 — ICVC Display Data (cont)
EXAMPLE 17 — ISM_CONF DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight
.
4. Press .
5. Enter password (4444 Factory Default).
6. Scroll down to highlight
.
7. Press .
DESCRIPTION
STATUS
UNITS
POINT
DEFAULT
Starter Type
0-3
starter
1
(0 = Full, 1 = Red, 2 = SS/VFD, 3 = VFD)
Motor Rated Line Voltage
200-13200
VOLTS
rlv
460
Volt Transformer Ratio:1
1-115
vt_rat
1
Overvoltage Threshold
105-115
%
overvolt
115
Undervoltage Threshold
85-95
%
undrvolt
85
Over/Under Volt Time
1-10
SEC
ovuntime
5
Voltage % Imbalance
1-10
%
v_unbal
10
Voltage Imbalance Time
1-10
SEC
vu_time
5
Motor Rated Load Amps
10-5000
AMPS
rla
200
Motor Locked Rotor Trip
100-60000
AMPS
mot_lra
1000
Locked Rotor Start Delay
1-10
cycles
lrs_del
5
Starter LRA Rating
100-60000
AMPS
str_lra
2000
Motor Current CT Ratio:1
10-1000
ct_ratio
100
Current % Imbalance
5-40
%
c_unbal
15
Current Imbalance Time
1-10
SEC
cu_time
5
Grnd Fault CT’s?
0/1
NO/YES
gf_cts
YES
Ground Fault CT Ratio:1
150
gfct_rat
150
Ground Fault Current
1-25
AMPS
gf_amps
15
Ground Fault Start Delay
1-20
cycles
gf_sdel
10
Ground Fault Persistence
1-10
cycles
gf_pdel
5
Single Cycle Dropout
0/1
DSABLE/ENABLE
1cyc_en
DSABLE
Frequency = 60 Hz? (No = 50)
0/1
NO/YES
linefreq
YES
Line Frequency Faulting
0/1
DSABLE/ENABLE
freq_en
DSABLE
MENU
SERVICE
ISM (STARTER) CONFIG DATA
SELECT
ISM_CONF
SELECT
Содержание AquaEdge 19XR series
Страница 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Страница 150: ...150 Fig 62 PIC II Control Panel Wiring Schematic Frame 2 3 4 and E Compressors without Split Ring Diffuser a19 1870 ...
Страница 152: ...152 a19 1871 Fig 63 PIC II Control Panel Wiring Schematic Frame 4 and 5 Compressors with Split Ring Diffuser ...
Страница 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Страница 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Страница 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Страница 163: ...163 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont a19 1880 ...
Страница 176: ...176 CONTINUED ON NEXT PAGE Fig 71 Typical Medium Voltage Variable Frequency Drive VFD Wiring Schematic cont a19 2064 ...
Страница 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Страница 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...