42
Table 3 — ICVC Display Data (cont)
EXAMPLE 23 — RAMP_DEM DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press
.
2. Press .
3. Scroll down to highlight
.
4. Press .
5. Scroll down to highlight
.
6. Press .
NOTE: No variables are available for CCN read or write operation.
EXAMPLE 24 — TEMP_CTL DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight
.
4. Press .
5. Scroll down to highlight
.
6. Press .
EXAMPLE 25 — ICVC CONFIGURATION TABLE
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight
.
4. Press .
NOTE: Default values are shown for configurable items.
DESCRIPTION
STATUS
UNITS
POINT
DEFAULT
Pulldown Ramp Type:
0/1
ramp_opt
1
Select: Temp=0, Load=1
Demand Limit and kW Ramp
Demand Limit Source
0/1
dem_src
0
Select: Amps=0, kW=1
Amps or kW Ramp% Min
5-20
%/MIN
kw_ramp
10
Demand Limit Prop Band
3-15
%
dem_prop
10
Demand Limit At 20 mA
40-100
%
dem_20ma
40
20 mA Demand Limit Opt
0/1
DSABLE/ENABLE
dem_sel
DSABLE
Motor Rated Kilowatts
50-9999
kW
motor_kw
145
Demand Watts Interval
5-60
MIN
dw_int
15
DESCRIPTION
STATUS
UNITS
POINT
DEFAULT
Control Point
ECW Control Option
0/1
DSABLE/ENABLE
ecw_opt
DSABLE
Temp Pulldown Deg/Min
2-10
^F
tmp_ramp
3
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA
–30- 30
^F
deg_20ma
10
RESET TYPE 2
Remote Temp —> No Reset
–40-245
DEG F
res_rt1
85
Remote Temp —> Full Reset
–40-245
DEG F
res_rt2
65
Degrees Reset
–30-30
^F
deg_rt
10
RESET TYPE 3
CHW Delta T —> No Reset
0-15
^F
restd_1
10
CHW Delta T —> Full Reset
0-15
^F
restd_2
0
Degrees Reset
–30-30
^F
deg_chw
5
Select/Enable Reset Type
0-3
res_sel
0
DESCRIPTION
STATUS
DEFAULT
Device Name
19XRPIC2
Description
19XR Centrifugal Chiller
Software Part Number
CESR-131294-xx
Model Number
text string
Serial Number
text string
Reference Number
VER xx
Bus Number
0
0
Address
1
1
Baud Rate
9600
9600
US Imp/Metric
US Imp
US Imp
Password
1111
1111
LID Language
ENGLISH
ENGLISH
MENU
SERVICE
EQUIPMENT SERVICE
SELECT
RAMP_DEM
SELECT
MENU
SERVICE
EQUIPMENT SERVICE
SELECT
TEMP_CTL
SELECT
MENU
SERVICE
ICVC CONFIGURATION
SELECT
Содержание AquaEdge 19XR series
Страница 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Страница 150: ...150 Fig 62 PIC II Control Panel Wiring Schematic Frame 2 3 4 and E Compressors without Split Ring Diffuser a19 1870 ...
Страница 152: ...152 a19 1871 Fig 63 PIC II Control Panel Wiring Schematic Frame 4 and 5 Compressors with Split Ring Diffuser ...
Страница 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Страница 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Страница 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Страница 163: ...163 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont a19 1880 ...
Страница 176: ...176 CONTINUED ON NEXT PAGE Fig 71 Typical Medium Voltage Variable Frequency Drive VFD Wiring Schematic cont a19 2064 ...
Страница 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Страница 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...