APPENDIX D — BACNET COMMUNICATION OPTION (cont)
Table D — Open System Wiring Specifications and Recommended Vendors
LEGEND
LOCAL ACCESS TO THE UPC OPEN CONTROL-
LER — The user can use a BACview
6
handheld keypad dis-
play unit or the Virtual BACview software as a local user inter-
face to an Open controller. These items let the user access the
controller network information. These are accessory items and
do not come with the UPC Open controller.
The BACview
6
unit connects to the local access port on the
UPC Open controller. See Fig. F. The BACview software must
be running on a laptop computer that is connected to the local
access port on the UPC Open controller. The laptop will re-
quire an additional USB link cable for connection.
See the
BACview Installation and User Guide
for instruc-
tions on connecting and using the BACview
6
device.
To order a BACview
6
Handheld (BV6H), consult Commer-
cial Products i-Vu
®
Open Control System Master Prices.
CONFIGURING THE UPC OPEN CONTROLLER'S
PROPERTIES — The UPC Open device and
Comfort
Link
control must be set to the same CCN Address (Element) num-
ber and CCN Bus number. The factory default settings for
CCN Element and CCN Bus number are 1 and 0 respectively.
If modifications to the default Element and Bus number are
required, both the
Comfort
Link and UPC Open configurations
must be changed.
The following configurations are used to set the CCN Ad-
dress and Bus number in the
Comfort
Link control. These con-
figurations can be changed using the scrolling marquee display
or accessory Navigator™ handheld device.
Configuration
→
CCN
→
CCN.A
(CCN Address)
Configuration
→
CCN
→
CCN.B
(CCN Bus Number)
The following configurations are used to set the CCN Ad-
dress and Bus Number in the UPC Open controller. These con-
figurations can be changed using the accessory BACview
6
display.
Navigation: BACview
→
CCN
Home: Element Comm Stat
Element: 1
Bus: 0
TROUBLESHOOTING — If there are problems wiring or
addressing the UPC Open controller, contact Carrier Technical
Support.
WIRING SPECIFICATIONS
RECOMMENDED VENDORS AND PART NUMBERS
WIRE TYPE
DESCRIPTION
CONNECT AIR
INTERNATIONAL
BELDEN RMCORP
CONTRACTORS
WIRE AND
CABLE
MS/TP
NETWORK
(RS-485)
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.
W221P-22227
—
25160PV
CLP0520LC
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
W241P-2000F
82841
25120-
OR
—
RNET
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
W184C-2099BLB
6302UE
21450
CLP0442
AWG
— American Wire Gage
CL2P
— Class 2 Plenum Cable
CMP
— Communications Plenum Rated
FEP
— Fluorinated Ethylene Polymer
TC
— Tinned Copper
Fig. F — BACview
6
Device Connection
A48-8583
Содержание AquaEdge 19XR series
Страница 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Страница 150: ...150 Fig 62 PIC II Control Panel Wiring Schematic Frame 2 3 4 and E Compressors without Split Ring Diffuser a19 1870 ...
Страница 152: ...152 a19 1871 Fig 63 PIC II Control Panel Wiring Schematic Frame 4 and 5 Compressors with Split Ring Diffuser ...
Страница 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Страница 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Страница 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Страница 163: ...163 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont a19 1880 ...
Страница 176: ...176 CONTINUED ON NEXT PAGE Fig 71 Typical Medium Voltage Variable Frequency Drive VFD Wiring Schematic cont a19 2064 ...
Страница 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Страница 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...