45
Constant Flow Surge Prevention
Normal Capacity Control Mode occurs when
ACTIVE
DELTA T
>
SURGE LINE DELTA T
.
Surge Prevention Mode Level 1 occurs when
ACTIVE
DELTA T
SURGE LINE DELTA T.
Surge Prevention Mode Level 2 occurs when
ACTIVE
DELTA T
+ 1
SURGE LINE DELTA T.
Variable Primary Flow Surge Prevention
Normal Capacity Control Mode occurs when
ACTIVE
DELTA TSAT
>
SURGE LINE DELTA TSAT
.
Surge Prevention Mode Level 1 occurs when
ACTIVE
DELTA TSAT
SURGE LINE DELTA TSAT.
Surge Prevention Mode Level 2 occurs when
ACTIVE
DELTA TSAT
+ 1
SURGE LINE DELTA TSAT.
The
VFD GAIN
parameter allows for additional adjustment
of the VFD response. Increasing
VFD GAIN
will increase the
rate of speed change.
For chillers equipped with VFDs there is an additional over-
current feature which is similar to Demand Limit Control. The
ICVC computes a projected value for motor current (VFD out-
put current, which is not measured by the ISM). The computed
value is based on
AVERAGE LINE CURRENT
and
TARGET
VFD SPEED
. The control then compares it to
VFD CURRENT
LIMIT
.
VFD CURRENT LIMIT
is a configurable entry in the
SETUP2 screen, representing VFD output current when the
line side current equals
RATED LOAD AMPS
and
VFD
SPEED
is at its maximum. The VFD Control Configuration
Job sheet includes the recommended value for
VFD CUR-
RENT LIMIT
, and that value may be further adjusted as de-
scribed under the VFD Control Verification section. (See
page 78.)
If
VFD LOAD FACTOR
(the ratio of estimated VFD output
current to
VFD CURRENT LIMIT
) exceeds 0.98, then drive
speed is increased until
VFD LOAD FACTOR
goes below 0.96,
or until maximum speed is reached. If
VFD LOAD FACTOR
exceeds 1.02 then the
GUIDE VANE POSITION
is made to de-
crease as well. This action ceases when the
VFD LOAD FAC-
TOR
subsequently drops below 1.0.
VFD LOAD FACTOR
is
displayed in the CONTROL ALGORITHM STATUS / CA-
PACITY screen.
NOTE: Increasing motor speed reduces motor amp draw. This
is the current between the VFD and the motor, NOT line cur-
rent. Generally for the case of
LINE VOLTAGE
equaling motor
voltage (460 volts), VFD output (motor) current is a few per-
cent higher than line current at full speed (60 Hz). As drive
speeds decrease from maximum, drive output voltage
decreases linearly with output frequency, and motor current
continues to increase relative to line current.
Table 5 — Guide Vane Delta Modes
The
TARGET VFD SPEED
,
ACTUAL VFD SPEED
and the
VFD GAIN
can be viewed and modified in the CAPACITY
display screen. The
TARGET VFD SPEED
can be manually
overridden by the operator from the COMPRESS screen. The
VFD MINIMUM SPEED
,
MAXIMUM SPEED
,
VFD GAIN
and
VFD INCREASE STEP
can be viewed and modified in the
SETUP2 display screen.
TARGET
and
ACTUAL VFD SPEED
can be viewed in the COMPRESS screen.
ECW CONTROL OPTION — If this option is enabled, the
PIC II uses the
ENTERING CHILLED WATER
temperature to
modulate the vanes instead of the
LEAVING CHILLED
WATER
temperature. The
ECW CONTROL OPTION
may be
viewed on the TEMP_CTL screen, which is accessed from the
EQUIPMENT SERVICE screen.
CONTROL POINT DEADBAND — This is the tolerance
range on the chilled water/brine temperature control point. If
the water temperature goes outside the
CHILLED WATER
DEADBAND
, the PIC II opens or closes the guide vanes until
the temperature is within tolerance. The PIC II may be config-
ured with a 0.5 to 2 F (0.3 to 1.1 C) deadband.
CHILLED
WATER DEADBAND
may be viewed or modified on the SET-
UP1 screen, which is accessed from the EQUIPMENT SER-
VICE table.
For example, a 1
F (0.6
C) deadband setting controls the
water temperature within ±0.5
F (0.3
C) of the control point.
This may cause frequent guide vane movement if the chilled
water load fluctuates frequently. A value of 1
F (0.6
C) is the
default setting.
A deadband is a span of measurement in which a controller
takes no action. In the PIC controls it is a temperature range
centered on the
CONTROL POINT
. If the
LEAVING
CHILLED WATER TEMP
falls within the
CHILLED WATER
DEADBAND
, the guide vanes will not move.
The purpose of the deadband is to prevent slight fluctua-
tions in
ENTERING CHILLED WATER TEMPERATURE
from keeping the guide vanes in constant movement.
Adjusting The Deadband — The default setting of the
CHILLED WATER DEADBAND
, is 1°F, which is 0.5° F above
and below the
CONTROL POINT
. The
CONTROL POINT
set-
ting range is 0.5 to 2° F. If temperature control is satisfactory
and the guide vanes are stable, do not change the setting.
When very close temperature control is required, as for
some process applications, the deadband may be reduced.
When constant small load changes occur in a system and
the vanes will not stabilize, increase the size of the deadband.
The deadband must always be smaller than the allowable drift
in leaving water temperature.
PROPORTIONAL BANDS — The proportional bands con-
trol how far the guide vanes will move in response to a specific
change in leaving water temperature. Increasing the propor-
tional band increases the amount that the water temperature
must move away from the control point in order to move the
guide vanes a specific amount. Decreasing the proportional
band allows the vanes to move the same amount with a smaller
change in water temperature.
If the proportional band is too large, the leaving water tem-
perature will increase or decrease slowly enough that the tem-
perature moves away from the control point by an unaccept-
able amount. A proportional band set too low will cause the
leaving temperature to overshoot the control point and cause
the guide vanes to “hunt.”
The PIC controls have separate proportional bands for in-
creasing and decreasing capacity. The
PROPORTIONIONAL
INCREASE BAND
should be set as described above. The
PRO-
PORTIONIONAL DECREASE BAND
should be set at a typi-
cally smaller value than the increasing band so that the guide
vanes can close quickly enough on a sudden drop in load to
prevent a low temperature safety trip.
Proportional Entering Chilled Water Gain — When Entering
Chilled Water Control is enabled the controls are resetting the
Leaving Chilled Water (LCW) control point every 10 seconds
GUIDE VANE
DELTA
NORMAL
CONTROL
MODE
SURGE
PREVENTION
MODE
IGV
POSITION
VFD
SPEED
IGV
POSITION
VFD
SPEED
From +0.2 to
+2.0
Increase
1st
Increase
when IGV
= max
Increase
only if VFD
speed =
max and if
hot gas
bypass is
present
and open
Increase
1st
From –0.2 to
–2.0
Decrease
when VFD
speed =
min
Decrease
1st
Decrease
Speed
decrease
not
allowed
Содержание AquaEdge 19XR series
Страница 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Страница 150: ...150 Fig 62 PIC II Control Panel Wiring Schematic Frame 2 3 4 and E Compressors without Split Ring Diffuser a19 1870 ...
Страница 152: ...152 a19 1871 Fig 63 PIC II Control Panel Wiring Schematic Frame 4 and 5 Compressors with Split Ring Diffuser ...
Страница 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Страница 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Страница 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Страница 163: ...163 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont a19 1880 ...
Страница 176: ...176 CONTINUED ON NEXT PAGE Fig 71 Typical Medium Voltage Variable Frequency Drive VFD Wiring Schematic cont a19 2064 ...
Страница 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Страница 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...