104
Table 16 — ICVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
H. OUT-OF-RANGE SENSOR ALARMS
STATE
PRIMARY MESSAGE
SECONDARY MESSAGE
PRIMARY CAUSE
ADDITIONAL
CAUSE/REMEDY
260
SENSOR FAULT
LEAVING CHILLED WATER
260->Sensor Fault: Check Leaving
Chilled Water Sensor
Check sensor resistance or voltage drop
against Table 17A or 17B.
Check for proper wiring between LEAVING
CHILLED WATER Temperature Sensor and
CCM J4-3 and J4-4. Check for disconnected,
grounded, or shorted wiring.
261
SENSOR FAULT
ENTERING CHILLED WATER
261->Sensor Fault: Check Enter-
ing Chilled Water Sensor
Check sensor resistance or voltage drop
against Table 17A or 17B.
Check for proper wiring between ENTERING
CHILLED WATER Temperature Sensor and
CCM J4-1 and J4-2. Check for disconnected,
grounded, or shorted wiring.
262
SENSOR FAULT
CONDENSER PRESSURE
262->Sensor Fault: Check Con-
denser Pressure Sensor
Check CONDENSER PRESSURE transducer
wiring. Confirm that 5 V reference signal is
available between CCM J2-4 and J2-6. Check
for disconnected, grounded, or shorted wiring.
Check for condensation in transducer
connector.
263
SENSOR FAULT
EVAPORATOR PRESSURE
263->Sensor Fault: Check Evapo-
rator Pressure Sensor
Check EVAPORATOR PRESSURE transducer
wiring. Confirm that 5 V reference signal is
available between CCM J2-1 and J2-3. Check
for disconnected, grounded, or shorted wiring.
Check for condensation in transducer
connector.
264
SENSOR FAULT
COMPRESSOR BEARING TEMP
264->Sensor Fault: Check Comp
Thrust Brg Temp Sensor
Check sensor resistance or voltage drop
against Table 17A or 17B.
Check for proper wiring between COMP
THRUST BRG TEMP Sensor and CCM J4-19
and J4-20. Check for disconnected, grounded,
or shorted wiring.
265
SENSOR FAULT
COMPRESSOR MOTOR TEMP
265->Sensor Fault: Check Comp
Motor Winding Temp Sensor
Check sensor resistance or voltage drop
against Table 17A or 17B.
Check for proper wiring between COMP
MOTOR WINDING TEMP Sensor and CCM J4-
23 and J4-24. Check for disconnected,
grounded, or shorted wiring.
266
SENSOR FAULT
COMP DISCHARGE TEMP
266->Sensor Fault: Check Comp
Discharge Temp Sensor
Check sensor resistance or voltage drop
against Table 17A or 17B.
Check for proper wiring between COMP DIS-
CHARGE TEMP Sensor and CCM J4-17 and
J4-18. Check for disconnected, grounded, or
shorted wiring.
267
SENSOR FAULT
OIL SUMP TEMP
267->Sensor Fault: Check Oil
Sump Temp Sensor
Check sensor resistance or voltage drop
against Table 17A or 17B.
Check for proper wiring between OIL SUMP
TEMP and CCM J4-21 and J4-22. Check for
disconnected, grounded, or shorted wiring.
268
SENSOR FAULT
COMP OIL PRESS DIFF
268->Sensor Fault: Check Oil
Pump Delta P Sensor
Check Oil Sump Pressure and Oil Pump Dis-
charge Pressure sensor wiring and accuracy.
Confirm that 5 V reference signal is available
between CCM J3-1 and J3-3 and J3-4 and J3-
6. Check for disconnected, grounded, or
shorted OIL PUMP DELTA P wiring.
269
SENSOR FAULT
CHILLED WATER FLOW
269->Sensor Fault: Check Chilled
Water Delta P Sensor
Check CHILLED WATER DELTA P transducer
wiring and accuracy. Check FLOW DELTA P
DISPLAY setting in SETUP1 screen. Confirm
that 5 V reference signal is available between
CCM J3-13 and J3-15 and J3-16 and J3-18.
Check for disconnected, grounded, or shorted
wiring. If pressure transducers are not installed,
check for presence of resistors and jumpers
CCM terminals J3-13 through J3-18. See
Chiller Controls Schematic if flow switches are
used.
270
SENSOR FAULT
COND WATER FLOW
270->Sensor Fault: Check Cond
Water Delta P Sensor
Check CONDENSER WATER DELTA P trans-
ducer wiring and accuracy. Check FLOW
DELTA P DISPLAY setting in SETUP1 screen.
Confirm that 5 V reference signal is available
between CCM J3-19 and J3-21 and J3-22 and
J3-24. Check for disconnected, grounded, or
shorted wiring. If pressure transducers are not
installed, check for presence of resistors and
jumpers CCM terminals J3-19 through J3-24.
See Chiller Controls Schematic if flow switches
are used.
271
SENSOR FAULT
VFD SPEED OUT OF RANGE
271->Sensor Fault: Check Actual
VFD Speed
Check 0 - 5 V DC input from VFD to ISM termi-
nals J6-1 and J6-2.
Check VFD speed feedback signal calibration.
Check VFD configuration, jumpers, and dip
switch settings. Check for disconnected,
grounded, or shorted wiring.
272
SENSOR FAULT
EVAP REFRIG LIQUID TEMP
272->Sensor Fault: Check Evap
Refrig Liquid Temp Sensor
Check sensor resistance or voltage drop
against Table 17A or 17B.
Check for proper wiring between EVAP
REFRIG LIQUID TEMP Sensor and CCM J4-11
and J4-12. Check for disconnected, grounded,
or shorted wiring.
Содержание AquaEdge 19XR series
Страница 69: ...69 Fig 33 19XR Leak Test Procedures a19 1625 ...
Страница 150: ...150 Fig 62 PIC II Control Panel Wiring Schematic Frame 2 3 4 and E Compressors without Split Ring Diffuser a19 1870 ...
Страница 152: ...152 a19 1871 Fig 63 PIC II Control Panel Wiring Schematic Frame 4 and 5 Compressors with Split Ring Diffuser ...
Страница 154: ...154 Fig 64 Benshaw Inc Wye Delta Unit Mounted Starter Wiring Schematic Low Voltage a19 1873 ...
Страница 161: ...161 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v ...
Страница 162: ...162 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont ...
Страница 163: ...163 Fig 69 Typical Low Voltage Variable Frequency Drive VFD Wiring Schematic 575 v cont a19 1880 ...
Страница 176: ...176 CONTINUED ON NEXT PAGE Fig 71 Typical Medium Voltage Variable Frequency Drive VFD Wiring Schematic cont a19 2064 ...
Страница 186: ...186 APPENDIX B LEAD LAG WIRING 19XR Lead Lag Schematic Series Cooler Flow a19 1655 ...
Страница 187: ...187 APPENDIX B LEAD LAG WIRING cont 19XR Lead Lag Schematic Parallel Cooler Flow a19 1717 ...