Appendix C. NL200/201 Settings
C-8
Telnet Timeout
This setting, in units of seconds, will determine how fast the configuration monitor
telnet session will time out if no activity is detected. Set to 0 for no time-out (not
recommended). (range 0..999)
Ping (ICMP)
The NL200/201 will not respond to “Ping” requests if this setting is disabled.
PakBus Address
This setting specifies the PakBus address for this device. The value for this
setting must be chosen such that the address of the device will be unique in the
scope of the datalogger network. Duplication of PakBus addresses in two or more
devices can lead to failures and unpredictable behaviour in the PakBus network.
When a device has a neighbour list or neighbour filter setting filled in for a port,
any device that has an address greater than or equal to 4000 will be allowed to
connect to that device regardless of the neighbour filter.
PakBus/TCP Server Port
This setting specifies the TCP service port for PakBus communications with the
datalogger. Unless firewall issues exist, this setting probably does not need to be
changed from its default value.
PakBus/TCP Password
Specifies the password that will be used to authenticate any incoming (server) or
outgoing (client) PakBus/TCP sessions. This password is used by the server to
generate a challenge to any client that connects to the PakBus/TCP server port. If
the client fails to respond appropriately, the connection will be terminated. If this
password is blank (the default value), no such authentication will take place.
PakBus/TCP Client Address (1-4)
This setting specifies the IP address of an outgoing PakBus/TCP client connection
that the NL200/201 should maintain. If the connection fails, the NL200/201 will
retry until the connection succeeds. No entry or a setting of 0.0.0.0 specifies that
no client connection will be made.
PakBus/TCP Client Port (1-4)
This setting specifies the TCP port of the outgoing PakBus/TCP client connection.
Typically, it is not necessary to change this entry from its default. (range 1..65535)
PakBus Routes
(read only)
This setting lists the routes that are known to the NL200/201. Each route known
to the NL200/201 will be represented by the following four components separated
by commas and enclosed in parentheses. The description of each component
follows:
Содержание NL200
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ...iv...
Страница 36: ...NL200 201 Network Link Interface 26...
Страница 42: ...Appendix B Cables Pinouts LED Function and Jumper B 4...
Страница 54: ......
Страница 60: ...Appendix D NL200 201 Driver Installation Instructions D 6...
Страница 62: ...Appendix E Sending a New OS to the NL200 201 E 2...
Страница 63: ......