User Manual
13
CS I/O PakBus Router
Connect to the NL200/201 in DevConfig (see Section 6,
Configuring the
NL200/201
).
On the NL200 tab:
o
Set Bridge Mode to “disable”.
On the CS I/O tab:
o
Set Configuration to “PakBus”.
o
Set SDC address. (Note that if multiple peripherals are connected to a
datalogger’s CS I/O port, each must have a unique SDC address.)
o
Set Beacon Interval and Verify Interval as described above. Often the
default values can be used.
On the Network Services tab:
o
Make note of the PakBus\TCP Server Port. (The default PakBus/TCP
Server Port is 6785. Unless firewall issues exist, it is not necessary to
change the port from its default value.)
7.1.3
LoggerNet Setup
In LoggerNet’s Setup Screen, press Add Root and choose “IPPort”. Input the
NL200/201’s IP address and port number. The IP address and port number
are input on the same line separated by a colon.
Add a PakBus Port (PakBusPort).
Add a PakBus Router (pbRouter). Input the PakBus address of the
NL200/201. The NL200/201’s default PakBus address is 678.
Add the datalogger and input the PakBus address of the datalogger.
Press Apply to save the changes.