Installation of the appliance must ensure easy access to service the appliance itself, the smoke channels and the flue.
Always maintain adequate distance and protection in order to prevent the product from coming into contact with water.
It is forbidden to install the stove in rooms with a fire hazard.
With the exception of sealed installations, it is also forbidden for liquid fuel appliances with continuous or inter-
mittent operation that draw the combustion air from the room they are installed in or B-type gas heating applian-
ces, with or without the production of domestic hot water, to coexist in the same room or in interconnecting rooms.
Sealed installation means that the product is certified as sealed and its installation (ducting
of the combustion air and connection to the chimney) is airtight with respect to the installa-
tion environment.
A sealed installation does not consume the room’s oxygen because it draws all the air from the outer environment (if suitably
ducted) and makes it possible to install the product in all houses that require a high degree of insulation such as “passive” or “high
energy efficiency” houses. Thanks to this technology there is no risk of smoke emissions in the room and no air inlets - hence not
even the relevant ventilation grilles - are required in the installation premises.
Consequently, there will be more draughts of cold air in the room, thus making it more comfortable and increasing the overall
efficiency of the system. The sealed stove in a sealed installation is compatible with the presence of forced ventilation or premises
that might have negative pressure with respect to the outside.
6.2
MINIMUM DISTANCES
Observe the distances from flammable objects (sofas, furniture, wood panelling, etc..) as specified in the following diagram.
If objects considered to be particularly sensitive to heat are present, such as furniture, curtains or sofas, as a precaution, increase
the stove clearances substantially to avoid possible deterioration due to the effect of heat.
Fig. 14 - Safety distances from combustible material.
.LEGENDA
dR (rear distance)
200 mm
dS (side distance)
300 mm
dB (lower distance)
0 mm
dC (upper distance)
750 mm
dP (front radiation)
1000 mm
dF (floor radiation)
1000 mm
dL (side radiation)
1000 mm
1
FLOOR
2
FRONT FLAMMABLE MATERIAL
3
AREA SUBJECT TO RADIATION