Allen-Bradley DF1 Protocol – PLC Error Code Tables
The following PLC error tables cover possible errors that are detected by the panel from Allen-
Bradley PLCs using the DF1 protocol. This includes full and half duplex communications for
the MicroLogix 1000, 1100. 1200 & 1500, SLC 5/03, /04, /05, ControlLogix, CompactLogix
and FlexLogix, and full duplex communications for the PLC5.
Note:
The following errors can be generated from the designated PLC, are monitored by the
C-more
Micro-
Graphic panel, and displayed on the panel’s screen as a hexadecimal value in panel error code P499, if active.
Please refer to the PLC users manual for additional information.
PLC generated error code for the Allen-Bradley DF1 Protocol continue on the next page.
A–7
Appendix A: Panel & PLC Error Code Tables
A
EA1-TCL-M Hardware User Manual, 1st Ed., 12/09
®
PLC Errors for Allen-Bradley DF1 Protocol, Local STS Errors (0-3 bits)
Panel Error Code
P499 Hex Value
Description
0x0
Success; no error.
0x1
DST node is out of buffer space.
0x2
Cannot guarantee delivery; link layer.
(The remote node specified does not ACK command.)
0x3
Duplicate token holder detected.
0x4
Local port is disconnected.
0x5
Application layer timed out waiting for response.
0x6
Duplicate node detected.
0x7
Station is offline.
0x8
Hardware fault.
PLC Errors for Allen-Bradley DF1 Protocol, Remote STS Errors (4-7 bits)
Panel Error Code
P499 Hex Value
Description
0x0
Success; no error.
0x10
Illegal command or format.
0x20
Host has a problem and will not communicate.
0x30
Remote node host is missing, disconnected, or shut down.
0x40
Host could not complete function due to hardware fault.
0x50
Addressing problem or memory protect rungs.
0x60
Function not allowed due to command protection selection.
0x70
Processor is in Program Mode.
0x80
Compatibility mode file missing or communication zone problem.
0x90
Remote node cannot buffer command.
0xA0
Wait ACK (1775 KA buffer full).
0xB0
Remote node problem due to download.
0xC0
Wait ACK (1775 KA buffer full).
0xD0
not used
0xE0
not used
0xF0
Error code in the EXT STS byte. See the error code table on the next page.
Содержание EA1-TCL-M
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 14: ......
Страница 60: ......
Страница 66: ......
Страница 118: ......
Страница 125: ...Notes 7 7 Chapter 7 Maintenance 7 EA1 TCL M Hardware User Manual 1st Ed 12 09 ...
Страница 126: ......
Страница 169: ......
Страница 170: ...B B C MORE MICRO GRAPHIC PANEL RUNTIME ERRORS AP APPENDIX APPENDIX In This Appendix Introduction B 2 Panel Errors B 2 ...
Страница 179: ......