3
Regulations
Logano GE615 - We reserve the right to make any changes due to technical modifications.
8
3
Regulations
3.1
Boiler room
3.2
Quality of heating water
V
For correct use and treatment of the fill and top-up
water, you MUST observe observe the operator's log,
which is included with the technical documentation.
z
Enter the amount and quality of the fill water in the log.
3.3
Disposal and recycling
z
If any heating system components need to be replaced,
they should be disposed of in an environmentally
responsible manner, via an approved disposal site.
z
Dispose of packaging in an environmentally
responsible manner.
Observe all standards and guidelines
applicable to the installation and operation of
this heating system in your country.
The information on the rating plate has
precedence and MUST be observed.
Caution: System damage
caused by frost.
z
Set up the heating system in a room safe
from the risk of frost.
Total boiler output Q
Ca(HCO
3
)
2
concentration
of the fill and top-up water
Maximum fill and top-up water
volume V
max
Heating water
kW
mol/ m³
m³
pH value
100
d
Q
d
350
d
2,0
V
max
= three times system volume
8,2 – 9,5
350
d
Q
d
1000
d
1,5
100
d
Q
d
350
> 2,0
V
max
= 0.0313 x Q / Ca(HCO
3
)
2
with: Q in kW and Ca(HCO
3
)
2
in
mol/ m³
350
d
Q
d
1000
> 1,5
Q > 1000
–
Tab. 4
Requirements for fill, top-up and heating water