4
Installation
Logano GE615 - We reserve the right to make any changes due to technical modifications.
11
4.3.1
Base and boiler plinth
Place the boiler on a 50 – 100 mm high base (observe
wall clearances). The base must be flat and level. The
front edge of the boiler should be flush with the edge of
the base.
If you are not using a boiler plinth (accessory), angled
steel sections (100 x 50 x 8 mm) or flat steel sections
(100 x 5 mm) must be put in place when installing the
base.
Fig 5
Base dimensions
A sound-absorbing plinth is available as an
accessory. The boiler plinth prevents the
transmission of vibrations to the base.
Number of
sections
L1 (base)
L2 (steel
section)
9
1670
1470
10
1840
1640
11
2010
1810
12
2180
1980
13
2350
2150
14
2520
2320
15
2690
2490
16
2860
2660
Tab. 9
Base dimensions for angled/flat steel sections