4
Installation
Logano GE615 - We reserve the right to make any changes due to technical modifications.
25
4.11.3 Fitting the burner door
In the factory, the burner door hinge lobes are fitted on the
right-hand side. For left-hand closing, dismantle the hinge
lobes from the right-hand side and reassemble them on
the left-hand side of the burner door.
V
Place a few drops of Silastik adhesive, 15 – 20 cm
apart, in the packing grooves on the front section.
z
Insert GP packing cord into the packing groove on the
front section. Position the packing cord joint at the
side.
z
Screw each hinge pin (right-hand closure) to the front
section with two hexagon bolts M12 x 55. For left-hand
closing, secure accordingly on the left-hand side.
z
Hook the burner door hinge lobes into the hinge pins.
Fig 29 Fitting the burner door
1
Hinge pin (top)
2
Packing cord joint (side)
3
Hinge pin (bottom)
4
Hinge lobe (bottom)
5
Holes in the burner door
6
Hinge lobe (top)
4.11.4 Inserting the hot gas baffles
V
Take hot gas baffles from the fittings case and insert
into the hot gas flue according to the inscription on
them (
Æ
see Fig. 30, Fig. 31, page 26, Fig. 32,
page 26 and Tab. 1, page 5).
Fig 30 Inserting the hot gas baffles (boiler block with 9
sections)
1
Hot gas baffles with sickle-profile (baffle part)
2
Hot gas baffles with sickle profile (hooked together)
The boiler, which consists of 16 sections,
does not contain any hot gas baffles.
A distinction is made between hot gas baffles
with a sickle profile and those with a
corrugated profile.
The hot gas baffles with a sickle profile come
in two parts. If equipping a hot gas flue with
sickle-profile baffles, you MUST ensure that
the two baffle parts are hooked together.
Æ
Fig. 31, page 26 shows the baffle parts
hooked together.