4
Installation
Logano GE615 - We reserve the right to make any changes due to technical modifications.
40
4.16.2 Installing the temperature sensor set
Both sensor wells have already been sealed in the flow
(
Æ
see section 4.7, page 20).
The sensors (controller sensor TRK, sensor STB and
Logamatic sensor FK or thermometer sensor) are inserted
into the sensor wells.
The sensors must be arranged as follows:
z
Push controller sensor TRK out of the sensor holder by
pressing it gently.
Fig 55 Temperature sensor set
z
Feed controller sensor into sensor well R½ " and
secure with a screw.
z
Feed both sensors, STB (high-limit safety cut-out) and
Logamatic FK, and the two sensor blanking pieces into
sensor well R¾ " and fix in place.
Fig 56 Installing the temperature sensor set
The STB sensor differs from the controller
sensor in that it has a side recess.
If using control panel 4212, the sensors must
be fed into the R¾ " sensor well. The R½ "
sensor well is not assigned if using this
control panel.
Содержание Logano GE615
Страница 57: ...8 Faults Logano GE615 We reserve the right to make any changes due to technical modifications 57 ...
Страница 58: ...8 Faults Logano GE615 We reserve the right to make any changes due to technical modifications 58 ...
Страница 59: ...8 Faults Logano GE615 We reserve the right to make any changes due to technical modifications 59 ...
Страница 60: ......