4.14
Boiler flue connections
This section describes how the boiler flue connections
are made.
4.14.1 Fitting the flue pipe sealing collar
(accessory)
z
Push the flue pipe as far as possible onto the flue gas
header outlet.
z
Place the flue pipe sealing collar around the flue pipe
and flue gas header outlet so that it overlaps at the top.
z
Place jubilee clips over the flue pipe sealing collar. One
of the jubilee clips must press onto the flue gas header
outlet and one onto the flue pipe.
z
Tighten jubilee clips. The flue pipe sealing collar must
fit smoothly and firmly in place.
Fig 37 Fitting the flue pipe sealing collar
1
Flue pipe sealing collar
2
Flue gas temperature sensor
3
Coupling
4
Flue pipe
5
Ubilee clips
6
Flue gas header
4.14.2 Fitting the flue gas temperature sensor
(accessory)
z
Weld the coupling into the flue pipe at a distance of
2 × flue pipe diameters (A) from the flue gas header.
z
Fit the flue gas temperature sensor as described in the
separate installation manual.
For better sealing of the boiler/flue pipe, we
recommend that you use the flue pipe sealing
collar (accessory).
Retighten the jubilee clips if required.