8.11 AC Error (Abnormal Operation: DHW Sensor)
Error
Description
DHW Sensor T3 error
Error is displayed when the DHW sensor has short-circuited or is disconnected
Checkpoint
Check if the DHW Thermistor connector is connected normally.
1. Control board wire
2. Heating water sensor wire
Measure and check the resistance of the Hot Water DHW Sensor (NTC method).
—
Separate the sensor and measure it at room temperature.
Check the DHW sensor for disconnection
Check the DHW sensor for short-circuit
Figure 40
Figure 41
Check the assembly
condition of the control board
and the temperature sensor
connector and reassemble
the control board and the
temperature sensor connector
Replace the temperature
sensor
Replace the temperature
sensor
Replace the control board
Check the
temperature
sensor for short
Is the
resistance of the
temperature sensor
normal?
Yes
Yes
No
No
86 °F: 40 kΩ (± error possible)
140 °F: 12.4 kΩ
185 °F: 3.9 kΩ