Indicator
Position
Description
Yellow
Left
System fault
Green
Center
Talk (green). Busy (Yellow
flashing).
Red
Right
System in emergency state,
call station disabled
Table 7.1: Call station status indicators
Emergency state
Emergency calls can only be distributed when the system is in the emergency state. See
section Enter the emergency state, page 91 for information about entering the emergency
state. In the emergency state, it is possible to distribute the following emergency calls:
–
Live speech with the emergency microphone of the voice alarm controller or remote
controls (see section Distribute live speech, page 92).
Notice!
It is not possible to distribute chimes or speech with the call station when the system is in
the emergency state, because the call station is disabled automatically at the moment that
the system enters the emergency state.
–
The default alert message (see section Distribute the alert message, page 94).
–
The default alarm message (see section Distribute the alarm message, page 96).
Notice!
It is also possible to distribute emergency calls using emergency trigger inputs. When an
emergency trigger input is activated, the system automatically enters the emergency state
and takes the action that is programmed with the configuration software.
Notice!
See the Configuration Software Manual for more information about the configuration
software.
Enter the emergency state
To enter the emergency state, push the emergency button on the front of the voice alarm
controller or the remote controls. The red LED that is integrated in the switch lights. The
emergency state can also be entered by pushing the Emergency button on the fireman’s panel.
Indicator test
EMG mic
Alert message
Alarm message
All call
Figure 7.8: Emergency button
7.4
7.4.1
Plena
Operation | en
91
Bosch Security Systems B.V.
Installation and Operation manual
2013.07 | V2.0 |