Fireman’s Panel
Current consumption:
150 mA (idle)
400 mA (indicator test)
Dimensions:
132.5 x 430 x 90 mm
Weight:
2.2 kg
End of line detection board
Input level:
100 V rms @ program 20 Hz - 20 kHz
Pilot input level:
5 V - 50 V @ 20 kHz ± 20%
Minimum trigger level:
3.5 V
Output:
Floating single trigger
Isolation:
250 Vp
Max level on open contact:
250 VDC
Response time:
Close min. 1 second
Close max. 10 seconds
Environmental conditions
Voice Alarm Controller
Operating temperature range:
-10 to +55 °C
Storage temperature range:
-40 to +70 °C
Relative humidity:
< 95%
Voice Alarm Router
Operating temperature range:
-10 to +55 °C
Storage temperature range:
-25 to +55 °C
Relative humidity:
< 95%
Call Station
Operating temperature range:
-10 to +55 °C
Storage temperature range:
-40 to +70 °C
Relative humidity:
< 95%