Clause / Requirement
Compliance
Signature
10.4 Indication of the voice alarm
zones in disablement condition
The indication for the disablement
condition in the voice alarm zone(s)
associated with each manual control
shall be available without any manual
action and shall not be suppressed. This
indication shall be by
Plena Voice Alarm System does not
support the optional disablement
condition.
a a separate light emitting indicator
(the general disablement indicator),
and
b an indication for each voice alarm
zone and/or an indication for
defined group(s) of zones.
11 Interface to external control device(s) (option with the requirements)
Clause / Requirement
Compliance
Signature
The VACIE may have provision for
interfacing to external control device(s)
such as standardized user interfaces
required by local regulations. In this case,
the following shall apply:
Plena Voice Alarm System does not
support the Interface to external
control device(s) option.
a the interface shall allow only access
level 1 and 2 functions;
b the mandatory functions of the VACIE
shall not be overridden;
c any short-circuit, interruption or earth
fault in the transmission path to the
external device(s) shall
– not prevent the mandatory
function of the VACIE, and
– be indicated on the VACIE, at least
by means of the general fault
warning indicator.
NOTE - The external control devices
should comply with available local or
national standards.
162 en | Appendices
Plena
2013.07 | V2.0 |
Installation and Operation manual
Bosch Security Systems B.V.