Clause / Requirement
Compliance
Signature
3 time and date of each fault
occurrence.
4 details of the fault found and the
circumstances of it being found (for
example during routine
maintenance).
5 action taken to rectify or remedy.
6 date, time and name of person in
charge of the system.
7 countersignature of the responsible
person, if any faults occurred or have
been rectified.
7.3 Maintenance
7.3.1 General
There shall be an established and
documented procedure for the scheduled
maintenance and retesting of the sound
system and equipment as recommended by
the system designer in conjunction with
the equipment manufacturer and in
accordance with relevant international and
national standards. It is recommended that
a minimum of two scheduled maintenance
inspections, by a competent person, be
made each year. A responsible person (see
4.2) shall be nominated to ensure that the
procedure continues to be carried out
correctly.
Responsibility of the installer to
establish the maintenance
procedures using the
manufacturer documentation.
7.3.2 Maintenance instructions
A stiff-covered maintenance manual should
be available giving details of all work
required to maintain the installation and
equipment in proper working order,
consistent with specified performance
criteria and any other requirements of this
standard and other relevant international
or national standards. This should state
clearly:
Responsibility of the installer to
establish the maintenance
procedures using the
manufacturer documentation.
a The method of maintenance.
b Any sequence related to maintenance.