Clause / Requirement
Compliance
Signature
13.10.1 Audible indicators shall be part of
the VACIE. The same device may be used
for voice alarm zone activated and fault
warning indications.
The monitor loudspeaker of the
Voice Alarm System is used for
both fault warning (continuous
tone) and emergency condition
(intermittent tone). If additional
sounders are desired, the installer
is responsible for connecting
sounders to output contacts
configured as ‘EVAC indicator’ or
‘fault indicator’. The installer may
decide to connect both the voice
alarm activated output contact as
well as the fault warning condition
activated output contact to the
same sounder.
13.10.2 The minimum sound pressure
level, measured under anechoic
conditions at a distance of 1 m, with any
access door(s) on the VACIE closed, shall
be
–
60 dBA for the voice alarm condition,
and
–
50 dBA for the fault warning
condition.
The installer is responsible for
either connecting a sounder that
complies with this clause outside
or inside the rack, or install the
system in a rack that is sufficiently
acoustic transparent. Advice is to
install a remote control panel, all
remote control panels and the
fireman’s panel have a monitor
speaker.
13.11 Indicator testing
Plena Voice Alarm System is
compliant.
All mandatory visible and audible
indicators shall be testable by a manual
operation at access level 1 or 2.
Plena Voice Alarm System provides
an ‘Indicator test’ button. When
activated all indications the system
and all its connected routers are
switched on to visually check the
indicators. The remote control
panels have their own test button.
The indicators of that remote
control panel and connected
extensions will light up.
The installer is responsible for
making indicators that are
connected to control output
contacts testable.
13.12 Audio performance
Plena Voice Alarm System is
compliant.
13.12.1 Output power
180 en | Appendices
Plena
2013.07 | V2.0 |
Installation and Operation manual
Bosch Security Systems B.V.
Содержание Plena Power Amplifier
Страница 1: ...Plena Voice Alarm System en Installation and Operation manual ...
Страница 2: ......
Страница 191: ......