Clause / Requirement
Compliance
Signature
13.3 Mechanical design requirements
Plena Voice Alarm System is
compliant.
13.3.1 The cabinet of the VACIE shall be
of robust construction consistent with
the method of installation recommended
in the documentation. It shall meet at
least classification IP30 of
EN 60529:1991+A1:2000.
The installer is responsible for
implementing this requirement for
19”-units, by means of using a
correct 19”- frame, meeting at
least classification IP30 of EN
60529:1991+A1:2000.
13.3.2 All interconnections and settings
inside the cabinet shall be accessible at
level 3.
If the installer ensures that the
physical access to the Plena Voice
Alarm System is restricted to
access level 3, all interconnections
and settings inside the cabinet
(e.g. interconnections between the
system elements) are accessible at
this access level.
13.3.3 The VACIE may be housed in more
than one cabinet. If the documentation
shows that the cabinets may be installed
in locations distributed within the
protected premises, then all of the
mandatory manual controls and
indicators shall be on one cabinet or on
cabinets declared to be only suitable for
mounting adjacent to each other.
The IUI shows that the Plena Voice
Alarm System cabinets may be
installed in locations distributed
within the premises. One
dedicated Plena Voice Alarm
System remote control panels with
extentions as needed, can then be
used for all of the mandatory
controls and indicators. The
installer is responsible for proper
installation in order to fulfill this
requirement.
13.3.4 All mandatory manual controls and
light emitting indicators shall be clearly
labeled to indicate their purpose. The
labels shall be legible at 0.8 m distance in
an ambient light intensity from 100 lux to
500 lux.
All indicators are clearly labeled.
For language other than English.
Permanent labels are available.
168 en | Appendices
Plena
2013.07 | V2.0 |
Installation and Operation manual
Bosch Security Systems B.V.