Clause / Requirement
Compliance
Signature
7.7.2.2 Following a reset operation, the
indication of the correct functional
condition corresponding to any received
signals shall either remain or be re-
established within 20 s.
After a reset operation, the Plena
Voice Alarm System will immediately
indicate the functional condition it is
currently in. It will also immediately
(<<1 s) respond to received signals
that will bring it into another
functional condition.
7.8 Output to fire alarm devices
(option with requirements)
This option is not supported by the
Plena Voice Alarm System.
In addition to the voice alarm outputs
the VACIE may have provision for the
automatic transmission of fire alarm
signals to fire alarm devices such as
beacons and vibrating devices. In this
case, the following shall apply:
a it shall be possible to de-activate the
fire alarm devices at access level 2;
b following de-activation, it shall be
possible to re-activate the fire alarm
devices at access level 2;
c the fire alarm devices shall not be
de-activated automatically;
d it shall be possible to configure the
VACIE at access level 3 to
automatically reactivate the fire
alarm devices if an alarm is reported
in an other zone.
7.9 Voice alarm condition output
(option with requirements)
Plena Voice Alarm System is
compliant.
The VACIE may have provision for
transmitting a signal that is in the voice
alarm condition. In this case, it shall
activate the output only in the voice
alarm condition.
The Plena Voice Alarm System
transmits a signal that it is in the
voice alarm condition via the Open
Interface, and via the status contact.
Plena
Appendices | en 149
Bosch Security Systems B.V.
Installation and Operation manual
2013.07 | V2.0 |