Voice Alarm Router
Electrical
Mains voltage:
230/115 V(AC), ± 10%, 50/60 Hz
Mains current:
0.2 A (system idle)
0.3 A (maximum load)
Max. mains inrush current:
1.5 A (for mains voltage of 220 - 240 V)
3 A (for mains voltage of 100 - 120 V)
Battery voltage:
20.0 to 26.5 V(DC)
Battery current:
0.5 A (system idle)
1.5 A (maximum load)
Notice!
Maximum load means maximum power out, maximum load 24 V(DC) out and maximum
number of call stations.
Interconnection
Voice Alarm Router:
RJ45 socket, CAN bus; max. 2 routers
External power amplifiers:
3-pin XLR and screw terminals, max. 5 A;
max. rated output 1000 W
Loudspeaker outputs
Type:
Screw terminals
Number of zones:
6
Number of loudspeaker lines:
12 (2 per zone)
Signal-to-noise ratio (flat at max. volume):
> 85 dB
Line voltage:
100 V
Overrides
Type:
3‑wire or 4‑wire on screw terminals
Voltage:
24 V(DC) for 4‑wire, if selected
Current:
Total 0.8 A
Trigger inputs / 24 V DC out
Trigger voltage:
< 24 V
Type:
Momentary or latching
Normally opened (default) or normally
closed
Emergency input supervision:
10 kΩ + 10 kΩ series and parallel resistors
24 V DC out:
24 V(DC), max. 0.8 A