Clause / Requirement
Compliance
Signature
b yellow for indications of
–
fault warnings, and
–
disablements, or
The Fault LED of Plena Voice Alarm
System controller, routers and
remote control panels are yellow.
Additionally the call station
indicator is also yellow when the
system is in the fault warning
condition. The installer is
responsible for connecting a yellow
light emitting indicator to the
‘Visual fault indicator’ output
contact (or another output contact
configured for this function).
Disablement indication is not
available in the Plena Voice Alarm
System since Plena Voice Alarm
System does not support the
optional disablement condition.
c green for the indication that the VACIE
is supplied with power.
All light emitting indicators of the
Plena Voice Alarm System that
indicate power supply are green.
NOTE - Where voice alarm automatic
message status indicators are provided, it
may be advantageous to indicate the
difference between evacuation and alert
messages. In this case, red will be used
for emergency messages and yellow may
be used for alert messages.
13.9.2 The use of different colors is not
necessary for indications on
alphanumeric displays. However, if
different colors are used for different
indications, the colors used shall be as
specified in 13.9.1.
The Plena Voice Alarm System do
not use alphanumeric displays.
13.10 Audible indications
Plena Voice Alarm System is
compliant.
Plena
Appendices | en 179
Bosch Security Systems B.V.
Installation and Operation manual
2013.07 | V2.0 |