
5.
Emergency call zone selectors:
Six buttons to select the zones to which the emergency call must be distributed (see
section Emergency state, page 91). Each button has a green and a red LED. The six red
LEDs indicate the zones that are selected for the emergency call. The six green LEDs
indicate the zones in which a business call is running.
6.
BGM zone selectors:
Six buttons to select the zones to which the BGM is distributed (see section Background
music, page 88). Each button has a green LED. The six green LEDs indicate the zones to
which BGM is distributed. It is not possible to control the volume of the BGM with the
remote control.
7.
All call button:
A button to select all zones. This button is only available in the emergency state (see
section Emergency state, page 91).
8.
Indicator test button:
A button to test all LEDs on the front panel of the remote control and all connected
remote control extensions. All LEDs are lit as long as the button is pushed (see section
Fault State, page 96).
9.
Emergency button:
A push button to put the system in the emergency state (see section Emergency state,
page 91).
10. Alert message button:
A button to select the alert message. This button is only available in the emergency state
(see section Emergency state, page 91).
11. Alarm message button:
A button to select the default alarm message. This button is only available in the
emergency state (see section Emergency state, page 91).
12. Microphone socket:
A socket to connect the hand-held emergency microphone (see section Emergency
microphone, page 49).
13. Bracket:
A bracket for the hand-held emergency microphone that is supplied with the remote
control.
14. Monitoring loudspeaker:
Built-in monitoring loudspeaker.
15. Ground:
A connection to electrically ground the remote control.
16. Firmware upgrade connector:
An RS232 connector to connect a PC to upgrade the firmware of the remote control.
17. Firmware upgrade switch:
A switch to upgrade the firmware of the remote control.
18. Remote control extension sockets:
Two redundant RJ45 sockets to connect remote control extensions to the remote control
(see section Remote control extensions, page 70).
19. Configuration settings:
A set of DIP switches to configure the remote control (see section Remote control, page
85).
20. Controller socket:
One RJ45 socket to connect the remote control to the voice alarm controller (see section
Voice alarm controller, page 70).
26
en | System overview
Plena
2013.07 | V2.0 |
Installation and Operation manual
Bosch Security Systems B.V.
Содержание Plena Power Amplifier
Страница 1: ...Plena Voice Alarm System en Installation and Operation manual ...
Страница 2: ......
Страница 191: ......