Page 5
APPROXIMATE
TEMPERATURE/TIME
RELATIONSHIPS TO
SCALDING
120°F (49°C) More than 5 minutes
125°F (52°C) 1
1
⁄
2
to 2 minutes
130°F (54°C) About 30 seconds
135
°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 1
1
⁄
2
seconds
155°F (68°C) About 1 second
Table 2: Scald Temperature/Time Relationships
SECTION II: GENERAL INFORMATION
WHEN YOU RECEIVE YOUR NEW WATER HEATER
Check the new equipment to see if all components are in good condition. If damage is
observed or parts appear to be missing, contact your wholesaler.
WATER TREATMENT/FILTRATION
In areas where poor water conditions are suspected (i.e. lime, iron, and other minerals), it is
essential that the water be tested and appropriate action taken to prevent damage to the
water heater and ensure the quality of the water.
TEMPERATURE CONTROL
The water heater is equipped with a main operating control that manages the temperature
regulating and limiting functionality. For domestic hot water, the proper temperature setpoint
is 120°F. For commercial applications, the maximum approved temperature setpoint is 180°F.
Sensors in the top of the tank measure water temperature. The control constantly compares
the sensor values to the temperature setpoint, and controls the burner power (on/off) and
modulation accordingly.
The manual reset, temperature limiting safety function is managed by the main operating
control. In the event that the tank temperature sensor reads 190°F, the control will shut off
all gas to the water heater. Manually reset the control to allow the heater to resume normal
operation. Should overheating occur and the gas supply fails to automatically lockout,
manually flip off the power switch.
The temperature setpoint is factory set at 120°F. If hotter water is required a tempering device
or anti-scald device must be installed at the domestic hot water outlet of the heater or at the
point of use. Table 2 details the approximate relationship of water temperature and time with
regard to scald injury. It is important for the user to understand the necessity of tempering or
anti-scald devices when using hotter water in domestic water heating systems.
CAUTION: Hot water in excess of 120
°
F can cause scalding!
Bock recommends
a tempering valve or anti-scald valve be installed and used according to
the manufacturer’s directions to prevent scalding. Many state and local codes now require
installation of these devices. Point of use temperature may be hotter than the setting on the
water heater thermostat. The tempering valve or anti-scald valve will ensure potable
water temperatures at the desired set point with a higher degree of accuracy.
Sh
ip
p
in
g W
ei
gh
t,
L
B
S (
kg
)