20
GB
4.5 TWO WIRES PHOTOCELL
Recognition of the two wires photocells must be activa-
ted in the menu b-4 to „2“!
One pair of two-wire photocells with a reaction time <500 ms
can be connected to the terminals „L-“ and „L+“.
The terminal designation represents the BERNAL photocell.
The connections for the receiver (RX) and transmitter (TX) are
replaceable.
For use of two-wire photocells and contact safety edges see
Figure 45.
Triggering of a photocell during opening is ignored. Triggering
of a photocell during closing leads to Stop and Reversing.
Recognition of the two wires photocell must be activa-
ted in the menu b-4 to „2“!
Recognition of the contact safety edge must be activa-
ted in the menu b-5 to „1“!
(see Figure 44)
Triggering of the photocell / safety edge during opening is ig-
nored. Triggering of the photocell / safety edge during closing
leads to Stop and Reversing.
! PROFESSIONAL EXTENSIONS !
Содержание G 501
Страница 1: ...1 USER MANUAL WWW BERNAL DE BERNAL GERMANY 8 8 GB G 501...
Страница 2: ...2 GB Your comfort is our drive...
Страница 50: ...50 GB OVERVIEW OF THE STRUCTURE OF THE MAIN MENU LEVEL 1 04...
Страница 51: ...51 GB SETUP SETTING FORCE DISTANCE TRAVEL PATH AND FORCE CURVE MENU P SEE 5 1 ff 05...
Страница 52: ...52 GB SETUP TRANSMITTERS PROGRAMMING A HAND TRANSMITTER MENU C 1 SEE 6 1 06...
Страница 53: ...53 GB SETUP TRANSMITTERS DELETE A HAND TRANSMITTER MENU C 2 SEE 6 2 07...
Страница 54: ...54 GB SETUP TRANSMITTER DELETE ALL TRANSMITTERS MENU C 2 SEE 6 2 08...
Страница 57: ...57 GB SPECIAL FUNCTIONS FUNCTION VENTILATION MENU S 1 TO S 3 SEE 7 5 1 11...
Страница 59: ...59 GB 13 DRIVE PARAMETERS MENU b SEE 8 ff...
Страница 60: ...60 GB 16...