Submenu DIAGNOSTICS
TAB3
Speed reference signal indication on term. 8 or 29 (dig. 9 Bit 0...511)
Input AN-IN/OUT term. 17 (configuration mode 1, see page 20)
Status of port E
Status of port A
Status of U27
Status of U31
Status of U1
Status of U2
Last error
2.nd error
1.st error
Software release NAME/REL Nr./DATE/TYPE (scrolling text)
Operating hours counter
Hours
Minutes
SUB DIAG
Function Aout: Analog output
TAB3
This parameter defines what the analog meter output (terminal 13) will indicate.
0: Output proportional to Fout. The frequency value corrisponding to full scale (10V)
can be set in TAB3, function Fm.
1: Output proportional to output current. Full scale (10V) = 200% of inverter rated
device current.
2: Digital frequency indication. Square wave signal corrisponding to the motor
frequency. (10V, duty cycle 50%). This parameter can only set, when the value in
TAB2, function SIO is OFF.
Range: 0...2
Default: 0
Function Fm: Full scale frequency value
TAB3
This parameter defines the full scale (10V) frequency value on the analog meter
output (terminal 13).
Range: 5...650 Hz
(10...1300 Hz *)
Default: 50 Hz
*Vers.D2A-1300-xxx
SUB DIAG
SOLL xx
ANA xx
Port E
Port A
STAT U27
STAT U31
STAT U1
STAT U2
Error1
Error2
Error3
Software:
XXXXX:XX
A.out 0
Fm 50.0Hz
BERGES electronic
44 Operating manual ACM D2/S2 09.07.2001
Содержание ACM S2
Страница 1: ...Operating manual ACM D2 S2 ...
Страница 2: ......
Страница 28: ...15 Programming ACM D2 S2 15 1 Program structure BERGES electronic 26 Operating manual ACM D2 S2 09 07 2001 ...
Страница 29: ...BERGES electronic 09 07 2001 Operating manual ACM D2 S2 27 ...
Страница 60: ...20 Notes BERGES electronic 58 Operating manual ACM D2 S2 09 07 2001 ...
Страница 61: ...BERGES electronic ...
Страница 62: ...BERGES electronic ...
Страница 63: ......