Function u: Frequency threshold FX2
TAB1
This parameter is used to program a frequency threshold FX2. The outputs OC1, OC2
or REL may be programmed to signalize motor speed equal or greather than FX2. The
threshold FX2 can also be used for automatic ramp switching (see TAB3, SUB XPAR,
function SW6).
For programming of the outputs see TAB3, functions OC1,OC2 und REL.
Range: 0...Fmax
Default: 10.0 Hz
Output current measurement
TAB1
The functions under the Submenu IMOT make possible measurement, displaying and
evaluate of the motor current.
To enter the submenu press both SHIFT and SELECT simultaneously.
Function I: Motor current indication
TAB1
This function indicates the actual inverter output current in % of the rated inverter cur-
rent.
The indication can be bypassed to function 1 of the main menu (see TAB3, func. DIS).
The output current can be indicated on the analog meter output
(terminal 13; 10V = 200% I
MOT
) (see TAB 3, function AOUT).
SUB IMOT
Function S: Current threshold
TAB1
This parameter defines a current threshold for the inverter (in % of the rated inverter
current).
The threshold can be set internally by means of the function S or externally by means
of an analog signal (0...10 V DC) applied to terminal 17 (input AN-IN/OUT).
Setting the external current threshold:
Set the threshold to 200% and then press the INC key once more. “rem xxx%” is now
shown on the display, whereby xxx corresponds to the setpoint at terminal 17.
The behaviour of the inverter when the output current exceeds the threshold is pro-
grammable (see TAB1, function S-INT). This condition can also be indicated on the
outputs OC1, OC2, REL. (see TAB3, function OC1, OC2, REL).
SUB IMOT
Range: 0...200% - rem
Default: 150%
u 10.0Hz
SUB IMOT
I 82.0%
S 150%
BERGES electronic
32 Operating manual ACM D2/S2 09.07.2001
Содержание ACM S2
Страница 1: ...Operating manual ACM D2 S2 ...
Страница 2: ......
Страница 28: ...15 Programming ACM D2 S2 15 1 Program structure BERGES electronic 26 Operating manual ACM D2 S2 09 07 2001 ...
Страница 29: ...BERGES electronic 09 07 2001 Operating manual ACM D2 S2 27 ...
Страница 60: ...20 Notes BERGES electronic 58 Operating manual ACM D2 S2 09 07 2001 ...
Страница 61: ...BERGES electronic ...
Страница 62: ...BERGES electronic ...
Страница 63: ......