Function 5: Acceleration time ramp 1
TAB1
This parameter sets the time to accelerate the motor from 0 to 50 Hz.
Use the following formula to determine the proper time for other frequencies:
Tx
=
50
∗
TACC
FEND
T
X
:
Time to set
T
ACC
: Acceleration time
F
END
:
End frequency
Ramp selection is controlled by terminal 25.
Range:
0.05...1000 sec.
Default: 2.5 sec.
Function 6: Deceleration time ramp 1
TAB1
This parameter sets the time to decelerate the motor from 50 to 0 Hz.
Use the following formula to determine the proper time for other frequencies:
Tx
=
50
∗
TDEC
FEND
T
X
:
Time to set
T
DEC
: Deceleration time
F
END
:
End frequency
Ramp selection is controlled by terminal 25.
Range:
0.05...1000 sec.
Default: 2.5 sec.
Function 7: Voltage/frequency ratio
TAB1
Sets the frequency (knee-point frequency) at which the maximum inverter output volt-
age is reached.
The maximum inverter output voltage depends on the mains voltage and on TAB2,
function MOD.
An incorrect setting of this parameter may lead to the damage
of the motor.
Range: 30...650 Hz
(30...1300 Hz *)
Default: 50 Hz
*Vers.D2A-1300-xxx
5 2.5s
Active ramp Terminal 25
ramp 1
ramp 2
OFF
ON
6 2.5s
Active ramp Terminal 25
ramp 1
ramp 2
OFF
ON
7 50.0Hz
ATTENTION!
BERGES electronic
09.07.2001 Operating manual ACM D2/S2 29
Содержание ACM S2
Страница 1: ...Operating manual ACM D2 S2 ...
Страница 2: ......
Страница 28: ...15 Programming ACM D2 S2 15 1 Program structure BERGES electronic 26 Operating manual ACM D2 S2 09 07 2001 ...
Страница 29: ...BERGES electronic 09 07 2001 Operating manual ACM D2 S2 27 ...
Страница 60: ...20 Notes BERGES electronic 58 Operating manual ACM D2 S2 09 07 2001 ...
Страница 61: ...BERGES electronic ...
Страница 62: ...BERGES electronic ...
Страница 63: ......