15.3. Program level TAB2
Program level TAB2
TAB2
The program level functions in TAB2 allows to configure analog and digital inputs and
to program the BOOST characteristic, the maximum output voltage and the security
features of the inverter.
Enter program level TAB3
TAB2
The program level functions in TAB3 allows to configure the outputs, to access the dia-
gnostic utilities and to program extended parameters.
To enter program level TAB3 press both SHIFT and SELECT simultaneously.
Function CLIP: Clipping of speed reference signal
TAB2
This parameter allows to cut the speed reference signal at lowest frequencies in order
to reduce the effect of noise on the speed reference line
A speed reference signal below the limit as defined by the fellowing formula is cut to
zero.
Limit =
N
∗
Fmax
512
N.... CLIP parameter value
Range: 0...15
Default: 2
Function FILTER: Speed reference filter
TAB2
The speed reference signal can be filtered by a digital filter. The line constant of the fil-
ter is set by this parameter.
Range: 0...6
Default: 3
TAB 2
SUB TAB3
CLIP 2
FILTER 3
BERGES electronic
38 Operating manual ACM D2/S2 09.07.2001