ATICS-DIO_D00080_03_M_XXEN / 04.2021 89
ATICS-…-DIO
9
Periodic verification and service
9.1
Periodic verification
The use of Bender products ensures protective measures against certain hazards when operating elec-
trical systems. The corresponding legal requirements are defined in the Ordinance on Industrial Safety
and Health (BetrSichV) and the supplementary Technical Rules (TRBS):
Every company is obliged to draw up a risk assessment for its work equipment (electrical systems and
equipment). With the help of the risk assessment, inspection intervals for the required periodic verifica-
tion are to be determined.
As a guide, TRBS1201 refers to DGUV (German Social Accident Insurance) regulations 3 and 4 as well as
to the supplementary DGUV regulations:
System/equipment
Inspec-
tion
interval
Type of inspection
Inspected by
Electrical systems
General
4 years
For safe condition.
According to applicable
electrotechnical rules
Qualified person
Electrical installations and stationary equipment
in "Special installations or locations" (DIN VDE
0100 Group 700)
1 year
According to TRBS1203, the tests must be carried out by a qualified person. The person carrying out the
test must have the training and professional experience required and must be able to recognise,
among other things, hazards caused by the inspection activity and the work equipment to be inspect-
ed.
The following periodic verification must be performed on electrical installations in compliance with the
applicable local or national regulations. If no local/national regulations apply, at least periodic verifica-
tion as recommended by DIN VDE 0100-710 (VDE 0100-710) should be performed.
Action
To be
performed by
Interval
Function test of the IT system monitoring by pressing the test button on
the corresponding operating units.
Medical
personnel
Once every
working day
(recommend-
ed by Bender)
Function test of the transfer switching device
For function test of the IT system monitoring on the monitoring device
see "„Settings menu 1: Changeover“ „8. Test interval“ on p. 68
Electrically
skilled person
Monthly (rec-
ommended by
Bender)
Содержание ATICS Series
Страница 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Страница 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Страница 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Страница 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Страница 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Страница 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Страница 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Страница 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Страница 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...
Страница 99: ...ATICS DIO_D00080_03_M_XXEN 04 2021 99 ATICS DIO 10 2 T V test report according to VDE 0100 Part 710...
Страница 100: ...100 ATICS DIO_D00080_03_M_XXEN 04 2021 Technical data 10 3 T V certificate regarding functional safety...