
30
ATICS-DIO_D00080_03_M_XXEN / 04.2021
Mounting and connection
4.1.4 Screw mounting on plate
i
Description applies to ATICS-…-DIO
i
• Observe dimension diagram of rear view.
• Use M5 mounting screws
I
C
aution
:
Screw heads or washers reduce voltage clearances.
Provide for sufficient clearance to live
conductors (voltage clearance) by using mounting screws with flat screw heads and flat washers. If
mounted on electrically conductive material: The mounting plate has to be earthed and the area un-
der the terminals has to be covered with insulating material.
It is the responsibility of the mounting staff to select the appropriate mounting plate and mounting
screws and to keep the prescribed torque setting.
4.2
Connection
4.2.1 Short-circuit protection
The choice of back-up fuses F should ensure both short-circuit protection for the transformer and the
selectivity to overcurrent devices downstream of the IT systems.
The connecting wires between the automatic transfer switching devices and the overcurrent protective
device downstream are to be laid so that they are short-circuit and earth-fault proof.
When choosing back-up fuses, observe both the maximum permissible values in accordance with the
applicable local regulations and national and international standards to make sure that the contacts are
weld-free.
For recommendations on the use of the appropriate fuse, refer to the nameplate of ATICS® and to the
ordering information in this manual.
!
1. Undo the Allen screws of the terminals (C).
2. Remove the green plug connectors (D) at top and
bottom.
3. Remove the black bridge (E) at the bottom.
4. Fasten the ATICS® to the mounting plate with M5
mounting screws (22 lb-in, 2.5 Nm) (see correspond-
ing dimension diagram).
5. Insert the black bridge (E), bottom.
6. Plug in the green plug connectors (D) top and bot-
tom.
7. Fix all terminals (C) with Allen screws.
Tightening torque: 5 Nm.
8. Fasten the terminal covers.
C
D
E
N
Содержание ATICS Series
Страница 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Страница 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Страница 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Страница 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Страница 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Страница 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Страница 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Страница 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Страница 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...
Страница 99: ...ATICS DIO_D00080_03_M_XXEN 04 2021 99 ATICS DIO 10 2 T V test report according to VDE 0100 Part 710...
Страница 100: ...100 ATICS DIO_D00080_03_M_XXEN 04 2021 Technical data 10 3 T V certificate regarding functional safety...