64
ATICS-DIO_D00080_03_M_XXEN / 04.2021
Menu mode: Operation and setting
7.3.2 Menu 2: Changeover
Display information on the changeover function (number, test). The device shows the alarm status for
each menu item: = no alarm, = alarm.
Menu
Description
Exit
Exit "Changeover" menu; go up one menu level
1. Changeover: xxx
Number of changeovers performed
2. Operat. time: xxh
Operating hours counter (h=hours, d=days, mo=months)
3. Changeover I>: xx
Number of changeovers performed which were carried out with overcurrent
of short-circuit current. These changeovers reduce the service life of the ATICS®
transfer switching device.
Currents in excess of 130 A (if an STW3 is used) or 250 A (if an STW4 is used) are
considered to be overcurrents or short-circuit currents.
4. TEST: dd.mm.yy
Date for next test (changeover)
5. Service: dd.mm.yy
Date for next service
6. TEST: dd.mm.yy
Date of the last test (TEST) or last changeover (LAST SWITCH).
7.3.3 Menu 3: History/Loggers
The device saves the history of alarm messages, measured values, settings, tests and service measures
in different memories (logger).
See the technical specifications for information about the maximum number of events which can be
saved from P. 95. Once the maximum number of events which can be saved is reached, the latest
event overwrites the oldest entry (entry 1).
Menu item
Function
Exit
Exit "History/Loggers" menu; go up one menu level
1. History
The "History" menu provides information about alarm messages and tests
performed. It also indicates whether an alarm is still pending or when it was ac-
knowledged by pressing the "mute" button on a CP9xx, a TM… alarm indicator
and operator panel or an MK… alarm indicator and test combination.
2. Data logger
Displays the history of measured values: Voltage line 1, voltage line 2,
switch position of the transfer switching device, load current downstream of the
transfer switching device I(3).
Содержание ATICS Series
Страница 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Страница 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Страница 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Страница 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Страница 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Страница 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Страница 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Страница 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Страница 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...
Страница 99: ...ATICS DIO_D00080_03_M_XXEN 04 2021 99 ATICS DIO 10 2 T V test report according to VDE 0100 Part 710...
Страница 100: ...100 ATICS DIO_D00080_03_M_XXEN 04 2021 Technical data 10 3 T V certificate regarding functional safety...