ATICS-DIO_D00080_03_M_XXEN / 04.2021 73
ATICS-…-DIO
Adjusting the settings:
Menu
Description
Exit
Exit settings menu "Relay"; go up one menu level
1. Function
ALARM
Relay switches if at least one of the following menus 3…9 is set
to "on" and the corresponding alarm message appears.
Active
Relay switches if at least one of the following menus 3…9 is set
to "on" and the corresponding alarm message does
not
appear
(operating message). If several of these menus are set to "on",
none of them must have an alarm in order to be able to activate
the
relay.
Application example:
Function = "Active"
Line 1 = "on", all other menus (line 2, device error, etc.) are set to
"off".
-> Relay is activated when line 1 is ready for operation.
GenSt
Relay is used as Generator start relay (
alarm relay 1 only
)
2. Relay mode
N/O
N/O operation. Relay only switches in the event of an alarm.
N/C
N/C operation. Relay only switches in the event of an alarm.
N/O-T
N/O operation. Relay switches in the event of an alarm or a test.
N/C-T
N/C operation. Relay switches in the event of an alarm or a test.
3. Line 1
on
Line 1
off
4. Line 2
on
Line 2
off
5. Manual mode
on
Relay switches in manual mode (transparent cover open or
digital input "Manual mode" selected).
off
6. Device error
on
Internal device error 1.x, 3.x (except 3.50), 6.x, 7.x, 8.x, 9.x or BMS
bus has no master, short-circuit distribution board, failure distribution board, test due,
service due.
off
7. Test interval
on
Relay switches when a test is due (interval elapsed).
off
8. Serviceinterv.
on
Relay switches when service is due (interval elapsed).
off
9. Dig. input
on
Alarm digital input. To ensure that the relay responds to the dig-
ital input, the functions "ALARM" or "R-OPL" must be additionally set in the "Settings
-> Dig. input" menu.
off
Содержание ATICS Series
Страница 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Страница 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Страница 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Страница 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Страница 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Страница 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Страница 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Страница 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Страница 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...
Страница 99: ...ATICS DIO_D00080_03_M_XXEN 04 2021 99 ATICS DIO 10 2 T V test report according to VDE 0100 Part 710...
Страница 100: ...100 ATICS DIO_D00080_03_M_XXEN 04 2021 Technical data 10 3 T V certificate regarding functional safety...