ATICS-DIO_D00080_03_M_XXEN / 04.2021 43
ATICS-…-DIO
5
Commissioning, settings and testing
5.1
Design and Installation
I
r
isk
of missing or incorrect displays on MK…, TM…, FTC… or CP9xx!
MK… alarm indicator and test combinations, TM… alarm indicator and operator panels or
COM460… BMS-Ethernet gateways which, together with an ATICS®, are connected to a BMS bus
must be provided with the latest operating software (e.g. MK800/TM800/MK2430 V 4.03 or higher).
Older MK…, TM… or FTC… cannot interpret the alarms of the ATICS® because the text modules re-
quired for the ATICS® are not integrated yet. These devices must either be updated or replaced. The
TMK-SET configuration software must also be the latest version.
I
r
isk
that the ATICS® does not switch!
The ATICS® requires enough current (2 pulses of 17 A for 30 ms) for a changeover. If there are several
ATICS® in one system, it is possible that the current is insufficient, especially when feeding from a
battery power supply. Set the delay time t(start) (P. 67) on the devices in such a way that after vol-
tage recovery the devices switch to the preferred supply one by one.
Provide at least two places for MK… alarm indicator and test combinations or TM… alarm indicator and
operator panels or CP9xx. These panels display messages from the ATICS® automatic transfer switching
device and monitor each other for failure. This is an essential part of the safety concept (functional safe-
ty, SIL2). Application examples of MK… or TM… in hospitals:
• Medical locations
• Continuously manned area (e.g. nurse service area)
• Technical area
Provide a fail-safe power supply for the MK… or TM… or CP9xx.
The TM… and MK… for the medical and technical area must be supplied with power from different
lines and sources. Example:
The MK… or TM… in medical locations is supplied from line 3 of the automatic transfer switching de-
vice. The MK… in technical areas is supplied from a fail-safe battery-supported line.
5.1.1 Setting parameters of indicator devices
i
Configure MK…, TM…, COM465, CP9xx in a meaningful way
In addition to the alarm, also configure a brief message of what to do or who to notify. Examples:
- IT system overload. Switch off unnecessary loads.
- IT system insulation fault. Call Building Services Tel. -123.
Indicator devices must display at least the following faults detected by the ATICS®:
• Failure line 1, failure line 2
• Device error, device failure ATICS®
• Device error with complete text or error code
Содержание ATICS Series
Страница 10: ...10 ATICS DIO_D00080_03_M_XXEN 04 2021 Intended use...
Страница 12: ...12 ATICS DIO_D00080_03_M_XXEN 04 2021 System description...
Страница 17: ...ATICS DIO_D00080_03_M_XXEN 04 2021 17 ATICS DIO...
Страница 21: ...ATICS DIO_D00080_03_M_XXEN 04 2021 21 ATICS DIO...
Страница 35: ...ATICS DIO_D00080_03_M_XXEN 04 2021 35 ATICS DIO ATICS 4 DIO...
Страница 37: ...ATICS DIO_D00080_03_M_XXEN 04 2021 37 ATICS DIO...
Страница 38: ...38 ATICS DIO_D00080_03_M_XXEN 04 2021 Mounting and connection ATICS 4 DIO...
Страница 39: ...ATICS DIO_D00080_03_M_XXEN 04 2021 39 ATICS DIO...
Страница 88: ...88 ATICS DIO_D00080_03_M_XXEN 04 2021 Periodic verification and service...
Страница 99: ...ATICS DIO_D00080_03_M_XXEN 04 2021 99 ATICS DIO 10 2 T V test report according to VDE 0100 Part 710...
Страница 100: ...100 ATICS DIO_D00080_03_M_XXEN 04 2021 Technical data 10 3 T V certificate regarding functional safety...