Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano
Cold
Rack/
Showc
ases
c22
"Superfrost": Temperature limit
("Shock freezing","Max. cooling
capacity").
- 40 ... 0 °C
0.0
0.0
0.0
c23
"Superfrost": Automatic switch-off
("Shock freezing","Max. cooling
capacity").
0: None, manual only
1: According to time
2: According to time or temperature
2
2
2
c30
Humidity sensor assignment.
Detailed description of the sensors
in parameters
H11
to
H47
.
0: None
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: Weighted average of F1 and F2
0
0
0
c31
Humidity setpoint.
0 … 100 % rH
50 %
50 %
50 %
c32
Humidity night switching (relative to
c31
.
-
20 … +20 %
0
0
0
c33
Humidity setpoint for Set2.
0 … 100 % rH
50 %
50 %
50 %
c34
Humidity mode.
0: Off
1: Evaporator fan on (continuous
operation)
2: Humidification
3: Dehumidification with reheating
1
1
1
c35
Humidity hysteresis.
0.1 % … 15.0 %
5.0 %
5.0 %
5.0 %
c36
Humidity hysteresis mode.
0: Symmetrical
1: One-sided
1
1
1
c37
Setpoint offset for reheating during
dehumidification (relative to cooling
space setpoint
c1/c2/c3
).
-
15.0 … 0.0 K
- 0.5
- 0.5
- 0.5
c38
Hysteresis for
c37
(one-sided,
below).
0.1 … 10.0 K
1.0 K
1.0 K
1.0 K
c39
Setpoint limitation
c31/c33
top.
c40
… 100 %
100 %
100
%
100
%
c40
Setpoint limitation
c31/c33
bottom.
0.0 % …
c39
0.0 %
0.0 %
0.0 %
c99
Password for parameter level
c--
-99 ... 999
0
0
0
d--
Defrosting control loop 1
Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold
Rack/
Showca
ses
d0
Assignment of evaporator sensor
(defrost sensor). Detailed description
of the sensors in parameters
H11
to
H47
.
0: None
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: Weighted average of F1 and F2
2
2
2
d1
Defrosting interval.
0: No automatic defrosting
1...99 h
3
3
3
d2
Type of defrosting.
0: No defrosting
1: Compressor off only (recirculation)
2: Electric
3: With hot gas
1
1
1
d3
Stop at defrost temperature.
0 ... + 30.0 °C
10.0
10.0
10.0
d4
Defrost time limitation.
1...99 min
30
30
30