Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold
Rack/
Showc
ases
b12
Input E1 inverse/non-
inverse.
0: Normal
1: Inverse
0
0
0
b13
Ext. function Switching
input E2.
See
b11
0
0
0
b14
Input E2 inverse/non-
inverse.
See
b12
0
0
0
b15
Ext. function Switching
input E3.
See
b11
0
0
0
b16
Input E3 inverse/non-
inverse.
See
b12
0
0
0
b17
Ext. function Switching
input E4.
See
b11
0
0
0
b18
Input E4 inverse/non-
inverse.
See
b12
0
0
0
b99
Password for level
b--
-99 ... 999
- 19
- 19
- 19
c--
Control loop 1
Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano
Cold
Rack/
Showc
ases
c0
Assignment of cooling space
sensor. Detailed description of the
sensors in parameters
H11
to
H53
.
0: None
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: Weighted average of F1 and F2
1
1
1
c1
Control loop: Setpoint for Set1.
c8…..c7
0.0
0.0
0.0
c2
Control loop: Night switching
setpoint (relative to actual setpoint
c1
/
c33
.
- 20 ... + 20.0 °C
5.0
5.0
5.0
c3
Control loop: Setpoint for Set2.
c8…..c7
2.0
2.0
2.0
c4
Switching direction.
0: Heating
1: Cooling
1
1
1
c5
Control loop: Hysteresis.
0.1...15.0 °C
1.5
1.5
1.5
c6
Control loop: Hysteresis mode.
0: Symmetrical
1: One-sided
1
1
1
c7
Upper setpoint limit.
c8
99 °C
15.0
15.0
15.0
c8
Lower setpoint limit.
- 99 °C...
c7
2.0
- 1.5
2.0
c10
Start protection after compressor
start.
0 ... 900 s
300
300
300
c11
Start protection after compressor
stop.
0 ... 900 s
120
120
120
c12
Compressor start protection after
mains on.
0 ... 60 min
0
0
0
c15
Duty cycle in emergency operation.
0 ... 100 %
50
50
50
c16
Cycle time in emergency operation.
5 ... 60 min
10
10
10
c20
Sensor assignment for “Superfrost"
(also core or product temperature)
Detailed description of the sensors
in parameters
H11
to
H53
.
0: None
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: Weighted average of F1 and F2
1
1
1
c21
"Superfrost": Time limit ("Shock
freezing","Max. cooling capacity").
1 ... 36 h
10
10
10